00:00:00.275 --> 00:00:08.900
This podcast is brought to you by the Indoor Environments Association, where science standards and community come together to improve the air we breathe and these spaces we live.
00:00:08.900 --> 00:00:11.942
To learn more and become a member, visit indoor environments.org.
00:00:11.942 --> 00:00:13.173
Enjoy the show.
00:00:16.495 --> 00:00:23.725
Welcome to episode one of the Indoor Environments Project, the podcast where we explore the spaces we live and the air we breathe.
00:00:23.725 --> 00:00:36.746
I'm your host, Diane Swecker, executive director of the Indoor Environments Association, and today we're diving into what we're calling houses from Heck, the kind of projects that test your pacience, your training, and sometimes even your sanity.
00:00:36.746 --> 00:00:49.195
This episode is packed with real world, great on mitigation, nightmares, unexpected challenges, lessons learned, and a few moments that might make you laugh, cringe, or totally rethink how you approach your next job.
00:00:49.195 --> 00:00:53.365
Joining us are two of the most respected voices in the field.
00:00:53.365 --> 00:01:02.679
Chad Robinson is the founder of Building Performance Company, a mechanical engineer by training and a nationally certified radon and vapor intrusion specialist.
00:01:02.679 --> 00:01:11.259
He's installed thousands of systems and currently trains the next generation of radon professionals at Kansas State University's Regional Radon Training Center.
00:01:11.259 --> 00:01:19.778
He's served in leadership roles both locally and nationally, including on the NRPP Certification Council and multiple standards committees.
00:01:19.778 --> 00:01:25.638
We're also joined by Joshua Kerber, environmental research scientist at the Minnesota Department of Health.
00:01:25.638 --> 00:01:33.448
Josh has more than two decades of experience in radon and indoor air quality with a background in atmospheric science and home construction.
00:01:33.448 --> 00:01:38.698
He's worked on everything from school testing and state licensing to international standards.
00:01:38.698 --> 00:01:47.013
He currently chairs the CRCPD's E 25 Committee on radon and has helped shape national and international policy on radon prevention.
00:01:47.013 --> 00:01:51.108
These two bring serious expertise and even better stories.
00:01:51.108 --> 00:01:52.828
let's get into it.
00:01:52.828 --> 00:01:54.278
Welcome Josh and Chad.
00:01:54.278 --> 00:01:54.759
So good.
00:01:54.759 --> 00:01:55.659
You can join us.
00:01:55.959 --> 00:01:56.438
Hello?
00:01:56.739 --> 00:01:58.149
Did I hear you say respected?
00:01:58.448 --> 00:01:59.049
Of course.
00:01:59.049 --> 00:01:59.918
Of course.
00:02:00.248 --> 00:02:00.438
Gosh..
00:02:00.438 --> 00:02:06.093
We're not even 90 seconds in, and Chad already has to have some audio that needs to be cut par for the course.
00:02:06.394 --> 00:02:09.813
So we're gonna start off with some icebreakers though.
00:02:09.813 --> 00:02:10.413
Welcome guys.
00:02:10.413 --> 00:02:11.704
Appreciate you being here today.
00:02:11.704 --> 00:02:17.943
Our first question is, what's your go-to snack or drink on a long field day?
00:02:17.943 --> 00:02:19.294
That's an important question.
00:02:19.593 --> 00:02:20.704
Super important.
00:02:20.704 --> 00:02:23.104
You gotta fuel the mind and body.
00:02:23.104 --> 00:02:31.993
I'm a peanut butter and honey sandwich guy because on a hot summer day when that honey starts to crystallize in there, it's so good.
00:02:31.993 --> 00:02:34.163
Yeah, just that and water, that's my go-to.
00:02:34.213 --> 00:02:41.829
I don't necessarily have to eat or snack, I'll just work through, but if I don't have my diet Mountain Dew at the ready I don't know.
00:02:41.829 --> 00:02:44.019
The brain starts to shut down or go backwards.
00:02:44.169 --> 00:02:44.903
I think you're addicted.
00:02:45.204 --> 00:02:45.864
That's key.
00:02:45.864 --> 00:02:48.813
You do often see Josh Kerber with a Diet Mountain Dew.
00:02:48.813 --> 00:02:52.114
90% of the population is addicted to coffee.
00:02:52.114 --> 00:02:53.924
Josh is addicted to Diet Mountain Dew.
00:02:53.924 --> 00:02:54.294
Yes.
00:02:54.354 --> 00:02:55.403
It's cheaper than coffee.
00:02:55.704 --> 00:02:56.003
Yeah.
00:02:56.003 --> 00:02:56.454
Yeah.
00:02:56.753 --> 00:02:57.883
Okay, next question.
00:02:57.883 --> 00:03:01.933
If you are mitigation Rig had a theme song, what would it be?
00:03:02.183 --> 00:03:02.993
Don't stop believing.
00:03:03.008 --> 00:03:03.834
Don't, don't Stop Believing.
00:03:04.183 --> 00:03:05.098
Oh, that's good.
00:03:05.299 --> 00:03:07.088
Why Chad, why did you say that?
00:03:07.389 --> 00:03:18.709
There was this really great Uber ride at the symposium one year and the two of us and Bruce and a few other people were crammed into this Uber.
00:03:18.709 --> 00:03:21.288
And the guy's like, what do y'all want to hear?
00:03:21.288 --> 00:03:22.998
And everybody's just kind of sitting there.
00:03:22.998 --> 00:03:28.618
Bruce says Journey, it was one of the greatest car rides ever.
00:03:28.618 --> 00:03:32.408
Because these just blasting, don't stop believing in the car.
00:03:32.408 --> 00:03:37.109
It's kind of been this group of us, it's been our theme song ever since then.
00:03:37.109 --> 00:03:49.169
We've worked really hard over the last few years to, in the hopes that the radon industry would take a step forward in their technical capacity and professionalism.
00:03:49.169 --> 00:03:52.419
We've tried to encourage that in the industry.
00:03:52.419 --> 00:04:03.818
To me, that's what that song means is for us in that instance is we're not gonna stop believing that we can push that professionalism and technical expertise forward.
00:04:04.118 --> 00:04:05.558
That people may not follow too.
00:04:05.558 --> 00:04:07.449
Like the hope is that they're gonna be there to follow.
00:04:07.449 --> 00:04:12.968
But ultimately to me, to add onto that, it's don't stop believing the numbers you get.
00:04:12.968 --> 00:04:18.908
If you start to understand the building science and why you're taking measurements and getting these numbers.
00:04:18.908 --> 00:04:24.009
Believe the numbers and understand them and it will set you free from a mitigation standpoint.
00:04:24.309 --> 00:04:25.358
Yeah, that's great.
00:04:25.358 --> 00:04:29.108
What is the weirdest thing you've ever found in a crawl space or attic?
00:04:29.259 --> 00:04:30.939
We're in crawl spaces all the time.
00:04:30.939 --> 00:04:36.488
Probably 50% of the houses we work on have crawl spaces, so there's weird stuff in them all the time.
00:04:36.488 --> 00:04:39.738
Dead cats that are just skeletons now.
00:04:39.738 --> 00:04:42.038
Glass, always is glass in there.
00:04:42.038 --> 00:04:55.119
But there was this one house that had an addition that was a crawlspace and we pulled out a contractor trash bag full of beer cans and vodka bottles.
00:04:55.119 --> 00:04:59.139
And I suspect that's what just went in there as they were building that thing.
00:04:59.139 --> 00:05:04.149
Somehow it was still standing and I mean, it was built like 30 or 40 years ago too.
00:05:04.149 --> 00:05:12.499
I was impressed that, they were able to put away that much alcohol and still build a thing that still is standing to this day.
00:05:12.699 --> 00:05:13.329
Amazing.
00:05:13.629 --> 00:05:20.319
In my line of work though, I'm not in the field every day like, like Chad may be, so I get called out to the weird houses.
00:05:20.319 --> 00:05:22.538
I'm not in a whole lot of crawl spaces.
00:05:22.538 --> 00:05:23.699
I delegate that.
00:05:23.699 --> 00:05:27.028
But on inspections, oftentimes you do gotta get in crawl spaces.
00:05:27.028 --> 00:05:30.088
On one inspection, I found, the hard way a leaky toilet.
00:05:30.088 --> 00:05:32.728
The public health part of me was like, okay, I gotta clean up.
00:05:32.728 --> 00:05:36.028
But then also, obviously let the homeowner know what you found.
00:05:36.028 --> 00:05:38.428
'cause I'm not there as a contractor.
00:05:38.428 --> 00:05:40.649
I'm there as a public health official.
00:05:40.649 --> 00:05:41.699
So that was one thing.
00:05:41.699 --> 00:05:45.928
I also found a ton of booze bottles in a homeowner's crawlspace.
00:05:45.928 --> 00:05:51.884
And no you do Chad on a daily basis when you find those things, but I inform the homeowner of what I find.
00:05:51.884 --> 00:05:57.884
And he tells me later that was the impetus of them talking with their kid about some alcohol abuse problems.
00:05:57.884 --> 00:06:02.863
And it was actually, a good thing in the end that I found that.
00:06:02.863 --> 00:06:06.173
Just doing normal public health work, just letting 'em know what I find.
00:06:06.173 --> 00:06:15.403
So that's more of a serious note, on a serious, yet funny note on an inspection, once I found Walmart shopping bags being used as poly to seal a crawlspace membrane.
00:06:15.704 --> 00:06:16.213
Wow.
00:06:16.514 --> 00:06:16.874
Yeah.
00:06:17.173 --> 00:06:17.564
Wow.
00:06:17.564 --> 00:06:19.783
What mill level do you think that is?
00:06:19.783 --> 00:06:20.894
Like 0.02?
00:06:20.894 --> 00:06:20.923
I
00:06:21.223 --> 00:06:22.394
don't even know.
00:06:22.394 --> 00:06:26.413
But yeah, it was super classy and it was right at the crawlspace entrance too.
00:06:26.413 --> 00:06:28.423
Nobody's gonna see it kind of thing.
00:06:28.423 --> 00:06:29.024
Right.
00:06:29.024 --> 00:06:29.954
It was ridiculous.
00:06:30.254 --> 00:06:31.663
I don't, that's a fine, that's a fine.
00:06:31.663 --> 00:06:31.783
I
00:06:32.084 --> 00:06:39.163
don't know if I've ever seen a Walmart bag that doesn't have a hole in it, let alone an entire crawlspace floor of bags that don't have holes in them.
00:06:39.463 --> 00:06:40.783
Exactly what I was thinking.
00:06:40.783 --> 00:06:42.494
Alright guys, so let's get into it.
00:06:42.494 --> 00:06:43.213
Let's kick off.
00:06:43.213 --> 00:06:47.144
So let's start off with the jobs that may haunt you.
00:06:47.444 --> 00:06:54.913
Yeah, and Diane, before we get into that, we maybe want to define what to us is a house from heck.
00:06:54.913 --> 00:07:00.413
We have in the industry have lovingly called houses that are difficult to fix houses from heck.
00:07:00.413 --> 00:07:09.598
In fact Daisy, had put a poll up on Nerds Facebook group and ask the question, what makes a difficult house to you?
00:07:09.598 --> 00:07:12.069
There was 25 respondents to that poll.
00:07:12.069 --> 00:07:18.178
One of the ones at the top of the list, like 16 of the 25 people said crawlspaces that don't have access.
00:07:18.178 --> 00:07:21.088
And it wasn't difficult to access.
00:07:21.088 --> 00:07:25.949
Or like inaccessible crawl spaces, like crawl spaces that are this tall.
00:07:25.949 --> 00:07:29.879
I say this tall and I'm showing you my hands and I forget that this is a podcast.
00:07:29.879 --> 00:07:30.869
You can't see that.
00:07:30.869 --> 00:07:34.569
But like you got six inches between the dirt and the floor joists.
00:07:34.569 --> 00:07:35.829
That's one scenario.
00:07:35.829 --> 00:07:36.459
That's tough.
00:07:36.459 --> 00:07:40.119
And sometimes, we could talk about that, but that's not what this podcast is about.
00:07:40.119 --> 00:07:47.394
But to me, and Josh and I have talked about this a lot, but to me, an inaccessible crawlspace does not make a house from heck.
00:07:47.394 --> 00:08:00.684
A client that is a pain in the butt doesn't make it a house from heck, a house that's a long ways away that you forgot to take the right size fan and pipe to, doesn't make it a house from heck.
00:08:00.684 --> 00:08:06.533
All those things make it difficult and you're losing money because of it, but it's not a house from heck.
00:08:06.533 --> 00:08:13.574
Your training hasn't necessarily taught you how to deal with the business side and maybe you lose some money, but that's not what we're referring to when we refer to a house from heck.
00:08:13.574 --> 00:08:25.834
To me, when we refer from to a house from heck, we're talking about one that has radon entry from a weird location or radon entry that doesn't happen consistently over time.
00:08:25.834 --> 00:08:34.173
So we have either radon coming in from somewhere other than where we normally think of it coming from, or it's coming in when we're not there to, see where it's coming in.
00:08:34.173 --> 00:08:36.453
Josh, I know you have some thoughts on this as well.
00:08:36.754 --> 00:08:44.514
Coming from the construction side of things, oftentimes hear I can't get suction to this far corner of the basement, and I always ask why.
00:08:44.514 --> 00:08:49.433
Because everything you're looking at when you go into a home is mostly lipstick and mascara.
00:08:49.433 --> 00:08:55.583
It's finished carpentry work, it's drywall, it's carpeting, it's some flooring that could be removed.
00:08:55.583 --> 00:08:57.803
You could do your work and then put it back.
00:08:57.803 --> 00:09:01.193
Now, are you gonna do that for your initial $1,200 bid?
00:09:01.193 --> 00:09:05.964
No, I understand that, but that also doesn't make it a house from, heck.
00:09:05.964 --> 00:09:09.413
You need to figure out a pipe route and finishing to wrap up a job.
00:09:09.413 --> 00:09:19.793
That's different than, I threw all my training and all of the expertise at this house, but it still has a radon problem at least some of the time, if not all of the time.
00:09:19.793 --> 00:09:24.264
And so then now those are the head scratchers that we talk about, that we refer to as a house from Heck.
00:09:24.313 --> 00:09:29.653
Those really difficult ones that kind of like you said, Josh, it's, you're left scratching your head.
00:09:29.653 --> 00:09:29.803
Yeah.
00:09:29.803 --> 00:09:31.663
You asked what is the one that haunts me?
00:09:31.663 --> 00:09:36.244
And I have to go to, the house we fondly refer to as Skipper.
00:09:36.244 --> 00:09:41.634
There's definitely people that will listen to this podcast that have heard about Skipper already.
00:09:41.634 --> 00:09:51.683
When we were working on this house, I called probably 10 or 15 different colleagues across the country looking for insights into what in the world could be going on.
00:09:51.683 --> 00:09:55.504
When we first got to this house, it's part of a real estate transaction.
00:09:55.504 --> 00:10:00.303
The buyers have not moved in yet, but the house has just sold.
00:10:00.303 --> 00:10:03.043
Radon levels are like 50 picocuries per liter.
00:10:03.043 --> 00:10:12.014
Normally those are the really easy houses to fix because there's a lot of permeability in the soil and we typically don't have a lot of permeability in the soil where we're at.
00:10:12.024 --> 00:10:14.663
Chad, where are you at when you're dealing with This home?
00:10:15.144 --> 00:10:17.063
We're right in the middle of Kansas.
00:10:17.214 --> 00:10:20.144
You're in the middle of what we'd call clay country.
00:10:20.144 --> 00:10:24.163
It's typically non-porous soils underneath your slabs.
00:10:24.644 --> 00:10:25.453
That's correct,
00:10:25.604 --> 00:10:25.693
yeah.
00:10:25.693 --> 00:10:27.884
Meaning clay or wet clay.
00:10:28.214 --> 00:10:28.423
Mm-hmm.
00:10:28.663 --> 00:10:31.339
IE expansive soils some people may call them.
00:10:31.639 --> 00:10:34.443
And we don't even backfill with gravel.
00:10:34.443 --> 00:10:40.563
We don't have any gravel close to where we're at, so we backfill with sand if we're lucky.
00:10:40.714 --> 00:10:57.744
In your area when you get blazing hot radon like 50, much higher than the four we're looking for obviously there's always some sort of air pocket because the house is drawing on something where it's on levels, in some pocket of air somewhere touching the foundation.
00:10:57.744 --> 00:11:03.323
You're not gonna get a lot of air flow through your substrates like you're, like we just mentioned.
00:11:03.323 --> 00:11:08.094
So there's something nearby that is always going to be the problem.
00:11:08.094 --> 00:11:08.813
Where is it?
00:11:08.813 --> 00:11:10.823
That's the issue you gotta figure out.
00:11:10.823 --> 00:11:14.844
And it may not be a big area, we may be only talking a, a couple of square feet.
00:11:14.844 --> 00:11:15.144
Right.
00:11:15.443 --> 00:11:15.774
Right.
00:11:15.774 --> 00:11:22.283
On this house, when we put the system in, I was really surprised that the soil under the house was.
00:11:22.283 --> 00:11:25.524
It wasn't even backfilled chunky sand or something.
00:11:25.524 --> 00:11:30.313
Every once in a while we'll have a river or sand that has a little bit of pea gravel.
00:11:30.313 --> 00:11:32.083
Occasionally we'll run across some pea gravel.
00:11:32.083 --> 00:11:40.144
Because this was 50 to start with, I expected, oh, we're gonna have some pea gravel and it must extend way out, away from the house somewhere or something like that.
00:11:40.144 --> 00:11:42.724
Because, or there's been a ton of settling somewhere.
00:11:42.724 --> 00:11:44.073
We didn't see any of that.
00:11:44.073 --> 00:11:46.173
The, there was no cracks in the foundations.
00:11:46.173 --> 00:11:51.153
This house was like, it was exactly the day it was built is, and it was built in 1963.
00:11:51.153 --> 00:11:54.783
To give everybody an idea, it's a rectangular, ranch house.
00:11:54.783 --> 00:11:59.254
28 feet deep and 45 feet long, the standard ranch house that you see all the time.
00:11:59.254 --> 00:12:01.953
It has a 20 by 20 crawl space on the back of it.
00:12:01.953 --> 00:12:08.644
Off to the right side of the standard rectangle part of the ranch house, there's a single car garage.
00:12:08.644 --> 00:12:16.994
On the back entry into the crawl space, there is a patio that's sitting on top of the foundation wall, so a possible radon entry point there.
00:12:16.994 --> 00:12:20.323
The front patio is also sitting on top of the foundation wall.
00:12:20.323 --> 00:12:22.183
So a possible radon entry point there.
00:12:22.183 --> 00:12:24.104
We know that going into this.
00:12:24.104 --> 00:12:26.114
We know there's possible radon entry points.
00:12:26.114 --> 00:12:30.524
We're not really worried about it because typically they don't cause problems for us.
00:12:30.524 --> 00:12:42.033
Anyway, we get there, we put the system in, we've got good suction under almost all of the slab of the basement, and we've got great suction in the crawl space.
00:12:42.033 --> 00:12:46.033
We don't address the two patios or the garage at this point.
00:12:46.033 --> 00:12:52.734
There's one corner of the basement that we've got like a pascal of negative pressure when we have a pascal of positive pressure without the fan.
00:12:52.734 --> 00:12:55.583
So baseline pressure of a pascal of positive.
00:12:55.583 --> 00:12:58.163
So we have some driving force for radon to come in.
00:12:58.474 --> 00:13:04.578
In, in your baseline, you're getting positive one pascal, kind of everywhere in the basement.
00:13:04.578 --> 00:13:08.149
And so you're trying to beat that positive one Pascal, with your radon system.
00:13:08.149 --> 00:13:09.198
You put it in.
00:13:09.198 --> 00:13:16.428
You do your pressure field extension testing and it shows that you've got negative pressure anywhere where you're testing through the floor, right?
00:13:16.729 --> 00:13:17.719
The time that we're there,
00:13:18.019 --> 00:13:18.239
yes.
00:13:18.239 --> 00:13:18.443
Okay.
00:13:18.443 --> 00:13:22.553
So you should be winning the radon game if the radons coming from underneath the floor.
00:13:23.004 --> 00:13:23.514
Correct?
00:13:23.933 --> 00:13:24.053
Yep.
00:13:24.053 --> 00:13:24.158
Okay.
00:13:24.458 --> 00:13:26.563
And where are we winning the radon game?
00:13:26.563 --> 00:13:27.254
So we come back.
00:13:27.254 --> 00:13:29.354
Yeah, I was gonna ask, were you winning the radon game then at that point?
00:13:29.688 --> 00:13:32.719
When they did the original test, it was summertime.
00:13:32.719 --> 00:13:36.889
When we were there to put the radon system in to begin with, it was the beginning of November.
00:13:36.889 --> 00:13:41.089
The radon levels post mitigation were 150.
00:13:41.089 --> 00:13:41.688
Whoa.
00:13:41.688 --> 00:13:41.869
Yikes.
00:13:41.869 --> 00:13:42.708
In Kansas.
00:13:42.708 --> 00:13:43.609
In Kansas.
00:13:43.609 --> 00:13:47.119
I have never seen, well, only one other time have I ever seen 150.
00:13:47.119 --> 00:13:49.649
And that wasn't a consistent 150.
00:13:49.649 --> 00:13:51.808
This was consistent 150.
00:13:51.808 --> 00:13:57.198
So the previous one I'd seen, we'd have spikes to 150, but it didn't stay that high all the time.
00:13:57.198 --> 00:13:58.759
This is weird, right?
00:13:58.759 --> 00:14:06.318
In order for tight soils to allow enough air movement to get up to 150, that is just weird and mind blowing.
00:14:06.318 --> 00:14:09.418
I can't imagine how this is working.
00:14:09.418 --> 00:14:12.759
First thing I do is I verify PFE.
00:14:12.759 --> 00:14:14.399
Because that's what we've gotta do.
00:14:14.399 --> 00:14:15.658
Do we have PFE?
00:14:15.658 --> 00:14:16.048
Okay.
00:14:16.048 --> 00:14:16.558
Yeah.
00:14:16.708 --> 00:14:18.389
Hey Chad, can I, can I interrupt?
00:14:18.389 --> 00:14:21.394
Most of us know, but can you explain what PFE is?
00:14:21.693 --> 00:14:24.264
PFE is, an acronym for pressure field extension.
00:14:24.264 --> 00:14:31.073
It's an amount of suction that we have under the slab created because of the radon system.
00:14:31.073 --> 00:14:44.813
If we change the pressure relationship in the house from the positive pressure in the soil to having negative pressure in the soil relative to the house, then the air in the house wants to go into the soil rather than the soil air wanting come into the house.
00:14:44.813 --> 00:14:53.874
That's the basics of everything we do is can we make the soil air go into the, or the house, air go into the soil instead of allowing the soil air to come into the house.
00:14:54.173 --> 00:14:54.323
Got it.
00:14:54.474 --> 00:14:57.203
We're doing that at this house except for.
00:14:57.203 --> 00:15:08.344
We don't know what's happening under the front and back patio slab, we don't know what's happening under the garage slab, but we're done chasing the crawlspace and we're done chasing the basement slab.
00:15:08.344 --> 00:15:16.734
Except for we don't know over time that the basement slab is always staying negative pressure relative to in the basement.
00:15:16.734 --> 00:15:24.234
To clarify, you said you're done chasing those two foundations because you've tested it for your pressure field and you're showing negative pressure anytime you're there.
00:15:24.234 --> 00:15:27.553
In all four corners of the basement and the crawlspace, you got it pegged.
00:15:27.553 --> 00:15:28.364
You're good to go.
00:15:28.364 --> 00:15:28.663
Right?
00:15:28.663 --> 00:15:29.563
Presumably right.
00:15:29.563 --> 00:15:33.162
In the end, those numbers on the surface, on paper show good signs.
00:15:33.162 --> 00:15:38.231
But it's your radon monitor over the next 2, 3, 4 days that are really gonna tell you how you won the game or not.
00:15:38.231 --> 00:15:41.261
We always have to verify with the radon test, that's the most important thing.
00:15:41.261 --> 00:15:42.701
We're fixing the radon problem, right?
00:15:42.701 --> 00:15:44.621
We had negative pressure, like we want.
00:15:44.621 --> 00:15:45.851
Not fixing the radon problem.
00:15:45.851 --> 00:15:53.442
I'm not gonna put in another suction point in the basement until I know for sure that the basement is belching every once in a while or something like that.
00:15:53.442 --> 00:15:58.101
We get out a data logger, that logs the pressure in the floor.
00:15:58.101 --> 00:16:03.142
We run a radon test and a pressure test over time, and we can compare those two sets of data.
00:16:03.142 --> 00:16:08.912
We found out that we always have negative pressure in the floor we don't always have negative radon.
00:16:08.912 --> 00:16:11.251
In fact, the radon is consistently elevated.
00:16:11.251 --> 00:16:16.692
This goes on for a couple weeks, a couple of back and forths, and it's beginning of December by this point.
00:16:16.692 --> 00:16:18.381
It's cold all the time.
00:16:18.381 --> 00:16:22.282
Radon novels in this basement are now 250 plus.
00:16:22.282 --> 00:16:26.721
And we don't know how high it is because our radon monitors only go up to 250.
00:16:26.721 --> 00:16:29.001
It may be even a little worse than that.
00:16:29.001 --> 00:16:33.302
The weird thing was we had a radon monitor in the center of the basement.
00:16:33.302 --> 00:16:35.761
We actually had 13 radon monitors in this house.
00:16:35.761 --> 00:16:40.461
At one point we had a radon monitor in the crawlspace, six radon monitors spread out through the basement.
00:16:40.461 --> 00:16:48.292
We had radon monitors upstairs above the crawlspace, radon monitors in the bedrooms, a radon monitor in the garage, and absolutely nothing showed off.
00:16:48.591 --> 00:16:50.871
It gave, the radon was just the same, pretty much everywhere.
00:16:51.172 --> 00:16:53.991
It wasn't really the same everywhere.
00:16:53.991 --> 00:16:56.111
The center of the basement was the highest.
00:16:56.111 --> 00:16:58.782
But none of the corners where you would think.
00:16:58.782 --> 00:17:00.682
We know that we're controlling the floor.
00:17:00.682 --> 00:17:06.112
We know that we're controlling the crawl space, so it's radon has to be coming in through the walls somewhere.
00:17:06.261 --> 00:17:06.622
Right.
00:17:06.622 --> 00:17:13.842
And you've got poured walls in all your houses down there because they've gotta be structurally sound enough to hold back the water and the clay.
00:17:14.142 --> 00:17:20.642
Almost all houses are poured concrete, we're not dealing with block wall foundations that are porous and that kind of stuff.
00:17:20.701 --> 00:17:20.942
Yeah.
00:17:20.942 --> 00:17:23.612
You're not gonna have a whole ton of air coming through your walls at all.
00:17:23.771 --> 00:17:30.102
If we have radon coming through the walls, it's likely that it's an intentional penetration.
00:17:30.102 --> 00:17:30.342
Right.
00:17:30.342 --> 00:17:33.821
Like a sewer line that's been abandoned or something like that.
00:17:33.821 --> 00:17:40.666
That's the kind of things we were looking for was where's the sewer line that's been abandoned or the hole in the wall.
00:17:40.817 --> 00:17:43.426
You also talked about the adjacent slabs too.
00:17:43.426 --> 00:17:45.227
You haven't touched on how you explored those.
00:17:45.636 --> 00:17:46.537
Yeah, good point.
00:17:46.537 --> 00:17:56.517
One of the first things we did, around the same time period where we got the data logger out we also put temporary systems on the front patio, the back patio, and in the garage.
00:17:56.517 --> 00:17:59.336
We got negative pressure between the garage and the house.
00:17:59.336 --> 00:18:05.156
And actually the garage system made the negative pressure in the basement even more negative.
00:18:05.156 --> 00:18:10.616
It was going down the wall between the basement and the house and creating more negative pressure under the basement slab.
00:18:10.616 --> 00:18:14.997
And we were getting great negative pressure under the front patio and under the back patio.
00:18:14.997 --> 00:18:18.116
We've taken all of those things out of the picture.
00:18:18.116 --> 00:18:20.027
We don't need those temporary systems.
00:18:20.027 --> 00:18:23.416
They're not affecting the, those areas are not affecting the radon problem.
00:18:23.416 --> 00:18:24.767
So where's the radon coming from?
00:18:24.767 --> 00:18:30.960
We know that everywhere that we've tested, we've got negative pressure relative to the house.
00:18:30.960 --> 00:18:33.410
We don't need to touch that anymore.
00:18:33.410 --> 00:18:41.009
But there's something somewhere, there's a conduit that's coming from somewhere that's allowing radon, allowing soil gas into your house.
00:18:41.529 --> 00:18:44.582
There's a preferential pathway still unaddressed somehow.
00:18:44.582 --> 00:18:46.422
But where the heck is it?
00:18:46.721 --> 00:18:46.991
Yeah.
00:18:46.991 --> 00:18:51.511
Up until this point, you haven't seen anything that would indicate that you have a source there for that.
00:18:51.511 --> 00:18:51.811
Right?
00:18:52.162 --> 00:18:52.551
Right.
00:18:52.551 --> 00:19:01.352
Chad ruled out any sources that may be stored there, whether it be pottery paints glow in the dark radium watches, rock collections, that kind of thing.
00:19:01.352 --> 00:19:02.211
That's all been removed.
00:19:02.211 --> 00:19:06.872
And you kind of know it that's been removed too in the fact that the radon levels jump around.
00:19:06.872 --> 00:19:14.402
Where if you have an internal source in the ventilation rate of a house kind of stays the same, your radon level in that case would stay roughly the same.
00:19:14.402 --> 00:19:16.412
It wouldn't jump around like in this case it did.
00:19:16.612 --> 00:19:17.001
Yeah.
00:19:17.001 --> 00:19:23.172
One of the conversations I had was with Bill Broadhead, and he's like, I've had a similar scenario to what you had".
00:19:23.172 --> 00:19:23.991
He's like.
00:19:23.991 --> 00:19:27.961
This house, was built early on, and it had a septic sewer system.
00:19:27.961 --> 00:19:31.372
They abandoned the septic sewer system and went to city sewer.
00:19:31.372 --> 00:19:37.102
And they just cut the pipe off inside the house and it was just open to the septic sewer.
00:19:37.102 --> 00:19:43.102
The drainage field out in the yard was just pumping soil gas in through this hole in the wall.
00:19:43.102 --> 00:19:49.832
The difference is, I found a hotspot in the house and I knew that I needed to cut the wall open in that area.
00:19:49.832 --> 00:20:02.652
And the homeowner was let's go ahead and cut the wall open." The other thing that I haven't explained is: there's carpet on, 75% of the floor of this basement, and three quarters of the walls are drywalled and finished.
00:20:02.652 --> 00:20:04.031
Actually, let me take that back.
00:20:04.031 --> 00:20:06.281
90% of the walls were drywalled.
00:20:06.281 --> 00:20:10.842
They ended up having a plumbing problem and they had to cut out drywall on one of the walls.
00:20:10.842 --> 00:20:13.511
I got to see inside the walls on a third of the walls.
00:20:13.511 --> 00:20:17.001
There's no plumbing pipes coming into the walls on that section.
00:20:17.001 --> 00:20:27.491
One other thing that it could be, again, something that Josh has reminded me about before is that if there was a well in this house, which is uncommon in our part of the country, but it happens occasionally.
00:20:27.491 --> 00:20:33.561
Then maybe it just didn't get covered up or capped off right and it's just letting radon come in.
00:20:33.561 --> 00:20:40.781
So I called the realtor and I was like, Hey, is there any way I could talk to the original owners of this house?
00:20:40.781 --> 00:20:42.192
And she's like, oh, they're older.
00:20:42.192 --> 00:20:45.102
Let me just give 'em a call and I'll ask if they had a well in there.
00:20:45.102 --> 00:20:45.912
She calls me back.
00:20:45.912 --> 00:20:50.251
Yeah, no, well, or any other plumbing situation or whatever.
00:20:50.251 --> 00:20:56.352
The homeowners did have a septic to begin with and they went to city sewer.
00:20:56.352 --> 00:21:02.192
After I talked to Bill, I explored that possibility forever and ended up finding absolutely nothing.
00:21:02.192 --> 00:21:08.672
I even stuck my sniffer down in the sewer clean out to see if there was high radon in the sewer.
00:21:08.672 --> 00:21:09.541
Nothing.
00:21:09.541 --> 00:21:12.311
It's less than ambient in the sewer.
00:21:12.311 --> 00:21:14.561
I'm okay, that's not what it is.
00:21:14.561 --> 00:21:16.662
I'm just scratching my head and.
00:21:16.662 --> 00:21:28.731
I ended up getting a Geiger counter from K State at one point from the radiation nuclear engineering department They loaned me a Geiger counter to see if any of the walls were hot somewhere.
00:21:28.731 --> 00:21:37.821
We're not gonna be able to see radon necessarily, but if there's a whole bunch of decay products plated out somewhere, maybe I'll be able to see some gamma coming through from that.
00:21:37.821 --> 00:21:38.902
Can't see anything.
00:21:38.902 --> 00:21:43.057
I scanned every inch of every wall and I'm not finding anything.
00:21:43.057 --> 00:21:44.436
I'm getting super frustrated.
00:21:44.436 --> 00:21:57.896
I actually have the radiation folks from the state of Kansas come out because I was like, these homeowners are gonna think that I'm absolutely incompetent at this point because I've been here for three months trying to figure this out.
00:21:57.896 --> 00:22:02.013
The state, radiation folks came out and it was awesome.
00:22:02.013 --> 00:22:05.973
For them to reassure the homeowners that we're doing the right thing.
00:22:05.973 --> 00:22:08.054
We're trying everything we can.
00:22:08.054 --> 00:22:13.003
They loaned me their $7,000 sniffer, which unfortunately never helped.
00:22:13.003 --> 00:22:14.525
But it was cool.
00:22:14.618 --> 00:22:18.483
Did it just tell you the same thing your own sniffer did, your much cheaper sniffer?
00:22:18.784 --> 00:22:19.564
More or less.
00:22:19.773 --> 00:22:21.334
So now how many gadgets are we at now?
00:22:21.334 --> 00:22:28.999
You're at a, you're at two sniffers, you're at a data logger, you're at all your different radon monitors, your 13 monitors your micro manometers.
00:22:29.298 --> 00:22:32.403
Yeah, probably four micro manometers.
00:22:32.403 --> 00:22:34.243
We've got what else?
00:22:34.394 --> 00:22:36.693
A ton detectors of one way or another.
00:22:36.693 --> 00:22:37.513
Pressure.
00:22:37.513 --> 00:22:38.263
Radon.
00:22:38.263 --> 00:22:39.074
Airflow.
00:22:39.374 --> 00:22:39.763
Yeah.
00:22:39.763 --> 00:22:46.153
There's also a company, they have made a device that's like an infrared camera for radiation.
00:22:46.153 --> 00:22:50.983
And I don't have the name of the company offhand, but they loaned me this device.
00:22:50.983 --> 00:22:58.144
I have no idea how much this thing costs, but they just mailed it to me and said, if you find the source because of this, it'll be good for us.
00:22:58.144 --> 00:23:02.354
And I was like, I really appreciate it and I will use it to see if I can find it.
00:23:02.354 --> 00:23:12.973
I left that there for several days and pointed it in different directions and left it set up for 24 hours as we moved around that house and tried to see if we could find any significant buildup of decay products.
00:23:12.973 --> 00:23:18.824
But the background was so high that it's just seeing radiation everywhere all the time.
00:23:18.824 --> 00:23:21.403
And it never found a source.
00:23:21.624 --> 00:23:28.253
Everything that you've had in your toolbox and all your friends' toolboxes have been thrown at this house.
00:23:28.253 --> 00:23:28.733
Yeah.
00:23:28.733 --> 00:23:30.804
It's still nothing, still no clear answers.
00:23:31.193 --> 00:23:31.374
And so.
00:23:31.374 --> 00:23:33.683
Until one thing happens...
00:23:33.733 --> 00:23:44.794
i'm talking to the homeowner at this point "I'm gonna have to cut open all of your walls and tear up all your carpet." And they're like, okay, if we need to do that, we'll do that." We were thinking about replacing the carpet anyway.
00:23:44.794 --> 00:23:50.344
They have a bunch of gun safes down there and that's gonna be the difficult part is to move the gun safes back off of the carpet.
00:23:50.344 --> 00:23:52.413
But we can make it happen if we need to.
00:23:52.413 --> 00:23:59.304
I know there's a conduit for radon somewhere and I'm not gonna just start putting suction points everywhere because it's not gonna help.
00:23:59.304 --> 00:24:03.503
We've already proved that all of the normal places aren't what's supplying the radon.
00:24:03.503 --> 00:24:12.294
One of the things that came outta the conversation with state of Kansas folks, was you have got to call the original owners of this house yourself.
00:24:12.294 --> 00:24:13.423
Yeah, you're right.
00:24:13.423 --> 00:24:14.634
I called the realtor back.
00:24:14.634 --> 00:24:22.554
I get the phone number for the people that own the house originally and get on the phone with the lady that built the house in 1963.
00:24:22.554 --> 00:24:25.713
She's still alive, and her mind is clear, as a bell.
00:24:25.713 --> 00:24:28.963
I asked her the first thing, "Is there a well in the basement by any chance?
00:24:28.963 --> 00:24:29.834
Or something like that.
00:24:29.834 --> 00:24:33.763
And she says, "oh yeah, there was a well in the basement 65 feet deep.
00:24:33.763 --> 00:24:39.733
We didn't have any water coming out of it, or not enough water, so we drill another well in the backyard." I said, wait a minute.
00:24:39.733 --> 00:24:49.794
I know about the one in the backyard, because I've stuck my sniffer in it and done all the things and tried to see if there's some way that there's radon getting from their end of the house.
00:24:49.794 --> 00:24:51.983
And she's yeah, that's the second well.
00:24:51.983 --> 00:24:59.794
I told you we had a first well in the house underneath the area where the water softener is." I was like, I've been all over the place...
00:24:59.794 --> 00:25:04.183
i've never lifted the brine tank on the water softener to see if it's underneath there.
00:25:04.183 --> 00:25:09.713
And I've had radon monitors in that area of the basement, right on top of the brine tank.
00:25:09.713 --> 00:25:12.144
And it came up less than in the middle of the house.
00:25:12.144 --> 00:25:13.203
I'm all confused.
00:25:13.203 --> 00:25:17.406
This is in the beginning of March, region seven has just happened.
00:25:17.406 --> 00:25:22.896
Josh came down for region seven and I was like, "Hey Josh, do you wanna go to this skipper house?
00:25:22.896 --> 00:25:30.747
On our way back to Salina", he's like, "yeah, I'd love to do that." I had just literally just found out that there was a well in this one corner of the basement.
00:25:30.747 --> 00:25:33.307
I go down there and I'm like, Josh, push the brine tank back.
00:25:33.307 --> 00:25:36.547
I'm gonna look underneath it and see if there's a well head under there.
00:25:36.547 --> 00:25:40.626
I stick my hand on the floor to balance myself to look underneath the brine tank.
00:25:40.626 --> 00:25:45.487
And there's air blowing on my hand, not from under the brine tank, but from the wall site.
00:25:45.487 --> 00:25:50.196
There's a wall right by the brine tank, and it's blowing from the wall.
00:25:50.196 --> 00:25:56.386
I'm confused and I'm like, Josh, I think I feel air blowing out from underneath this wall.
00:25:56.386 --> 00:26:01.557
He sticks his hand down there and he says, yeah, there's air blowing from out from underneath the wall.
00:26:01.557 --> 00:26:08.856
I get a knife or a scraper or something, I start messing around and there's all this rotten wood that I hadn't noticed before.
00:26:08.856 --> 00:26:11.116
I pick at it a little bit and it goes plunk.
00:26:11.116 --> 00:26:17.987
65 feet down into the well hole, it's wide open underneath the wall, this well head.
00:26:17.987 --> 00:26:21.856
We eventually end up cutting out the wall and capping that and everything.
00:26:21.856 --> 00:26:31.886
When Josh and I were there, we were estimating that there was probably 10 CFM coming out of that wellhead just naturally, it was 1700 picocuries per liter in that well.
00:26:31.886 --> 00:26:40.616
That's enough to supply 255 PICOCURIES per liter to the entire basement of this house and 90 or a hundred picocuries per liter upstairs.
00:26:40.767 --> 00:26:48.896
Within 15 inches of that well head, you had a hole through the floor measuring pressure, field extension, and it showed that you had negative pressure.
00:26:49.317 --> 00:26:55.497
I did have negative pressure eight inches away from the wellhead, but not in the wellhead.
00:26:55.497 --> 00:27:03.967
I have like five pascals of negative pressure, which is enough for any season to fix the radon problem, but it doesn't, didn't go down into the wellhead.
00:27:03.967 --> 00:27:08.166
So we just capped the wellhead, applied suction to the wellhead radon problem goes away.
00:27:08.166 --> 00:27:12.366
We probably didn't have to do anything else to the entire house.
00:27:12.366 --> 00:27:15.192
But we didn't know it was there because it was buried underneath the wall.
00:27:15.612 --> 00:27:17.791
What challenge skipper was, for sure.
00:27:17.791 --> 00:27:22.061
How long was your whole time there from beginning to mitigation completion?
00:27:22.362 --> 00:27:23.201
Four months.
00:27:23.501 --> 00:27:28.241
And imagine the prior homeowner stayed in, lived in that house for 40 years,
00:27:28.632 --> 00:27:29.352
60 years.
00:27:29.352 --> 00:27:30.821
The house was built in 63.
00:27:31.122 --> 00:27:31.842
Wow.
00:27:31.842 --> 00:27:32.711
Wow.
00:27:32.711 --> 00:27:33.311
Wow.
00:27:33.372 --> 00:27:33.731
That's an.
00:27:33.731 --> 00:27:34.632
Amazing.
00:27:34.632 --> 00:27:38.951
I'm sure you don't have many like that, Chad, but boy, that was a, that was an adventure for you.
00:27:38.951 --> 00:27:41.201
I would be out of business if they were all like that.
00:27:41.201 --> 00:27:42.852
We know that wells are a problem.
00:27:42.852 --> 00:27:45.971
It's just finding the Well that was the problem.
00:27:46.122 --> 00:27:52.332
And more common construction nowadays that we don't have wells within the living structure of the building.
00:27:52.332 --> 00:27:59.037
They're outside, but all around the country, there are wells within the walls of the building.
00:27:59.037 --> 00:28:10.076
And if that's the case, that well shaft goes down dozens if not hundreds of feet into fractured earth, which is just a basic water filled cave.
00:28:10.076 --> 00:28:12.896
And if it's not full of water, it's full of soil gas.
00:28:12.896 --> 00:28:18.386
And those things can pump tons of radon in and out of the basement very quickly.
00:28:18.386 --> 00:28:21.086
And you just happen to find one or another one.
00:28:21.491 --> 00:28:22.692
And hidden pretty well.
00:28:22.696 --> 00:28:47.787
The takeaway from all of that is if we weren't doing diagnostics as part of this, if we didn't know what the suction pressures were, we would've just had to give up because there's no way we would've just put suction points all over the basement and had systems on the front patios and back patios and everything, and we would've never found the problem because we wouldn't know that, oh yeah, all this other extraneous stuff is not actually doing any good.
00:28:47.936 --> 00:28:53.487
That's a very common response though in the industry is that we're just gonna add a suction point in an area.
00:28:53.487 --> 00:29:00.186
We think where the radon might be coming in next, where you think it's coming in without actually verifying, is a foolish decision.
00:29:00.186 --> 00:29:01.747
'cause you're just gonna be chasing your tail.
00:29:01.747 --> 00:29:06.247
You actually ruled out the fact that we don't need any more because we have it captured.
00:29:06.247 --> 00:29:07.747
There's something else going on.
00:29:07.747 --> 00:29:19.946
It's actually, it took a little bit more time, but it's a way less intrusive process in this regard, than just throwing arbitrarily suction point 2, 3, 4, or system two or three on a house.
00:29:19.946 --> 00:29:23.007
I cringe when I see more than one system on a single family home.
00:29:23.007 --> 00:29:24.207
It's usually never needed.
00:29:24.207 --> 00:29:28.356
But contractors will do it because they don't know any better.
00:29:28.356 --> 00:29:31.176
They're not confident in their ability to get the proper numbers.
00:29:31.477 --> 00:29:31.777
Right.
00:29:31.781 --> 00:29:33.551
Chad, you were very methodical going through it.
00:29:33.551 --> 00:29:38.652
If I were the homeowner, and how you explained it you checked every box that you had to go through.
00:29:38.652 --> 00:29:39.912
Every gadget was used.
00:29:39.912 --> 00:29:42.071
As a homeowner, you were the right guy to be there.
00:29:42.372 --> 00:29:43.511
We'd like to think so.
00:29:43.511 --> 00:29:51.336
And that's, that's honestly, that's the way the entire industry should be, is like we know what we're doing, we're professional about it.
00:29:51.336 --> 00:29:55.207
We're technical experts in the field that we're working in.
00:29:55.207 --> 00:30:01.866
And all of those tools in the toolbox are the things that we use to fix this problem.
00:30:01.866 --> 00:30:05.326
And it's not every house that has these kind of problems.
00:30:05.326 --> 00:30:15.616
But the ones that come up, if we can't fix 'em, then the homeowner's lose faith in our entire industry because they're like, "we had a house they just said it was too hard to fix." And that should never be the case.
00:30:16.007 --> 00:30:16.217
Yeah.
00:30:16.217 --> 00:30:17.086
It should never be the case.
00:30:17.086 --> 00:30:18.886
'cause there's not a house we can't fix.
00:30:18.886 --> 00:30:20.957
The numbers will guide the decisions.
00:30:20.957 --> 00:30:25.366
If you apply the building science properly, you're gonna fix every house, period.
00:30:26.106 --> 00:30:33.382
Before we jump into the next story, I want to take a quick moment to thank our listeners and share something that makes this conversation—and this entire podcast—possible.
00:30:33.382 --> 00:30:37.573
Being part of the Indoor Environments Association means you’re not alone.
00:30:37.573 --> 00:30:47.405
You’re joining a network of over 1,000 professionals who care about indoor air quality and are working together to grow their businesses, increase public awareness, and influence public policy.
00:30:47.405 --> 00:30:52.083
Join today and get access to the IEA Community, your peers, and your future allies.
00:30:52.083 --> 00:30:56.398
Just one hundred and ninety nine dollars a year—that’s only $16.59 cents a month.
00:30:56.398 --> 00:30:58.906
Visit indoorenvironments.org to become a member.
00:30:58.906 --> 00:31:00.625
Now, let’s get back to the episode.
00:31:01.404 --> 00:31:02.221
Really logical.
00:31:02.221 --> 00:31:03.392
Alright, what's next?
00:31:03.692 --> 00:31:10.122
There's handfuls of projects, I mentioned earlier in the podcast that, I don't get to see kind of the normal projects.
00:31:10.122 --> 00:31:13.571
Contractors call me when they run into problems like Chad called me.
00:31:13.571 --> 00:31:17.781
I get contractors locally that'll call Hey, I've got a difficult project.
00:31:17.781 --> 00:31:18.922
I've done X, Y, and Z.
00:31:18.922 --> 00:31:24.467
Can you come help me?" I don't see normal projects, like a drain tile system up and out.
00:31:24.467 --> 00:31:25.576
Real simple things.
00:31:25.576 --> 00:31:31.396
I see real complex houses, multiple foundations, giant houses, castles on lakes.
00:31:31.396 --> 00:31:37.376
I deal with clay soils, wet soils to sandy soils, to gravel soils, you name it.
00:31:37.376 --> 00:31:38.737
We have it all up here.
00:31:38.737 --> 00:31:45.037
When in this case it skipper Chad ran into kind of an airflow, a higher flow than he would normally expect to see.
00:31:45.037 --> 00:31:50.257
He deals with usually low airflow systems where I can deal with big airflow systems.
00:31:50.257 --> 00:31:56.011
Systems where we have pressure field extension almost all the time except when we don't.
00:31:56.011 --> 00:32:00.801
It's a whole different, our other side of the spectrum monster than what Chad could run into.
00:32:01.112 --> 00:32:10.132
Before you continue on that thought, you said I had a higher airflow situation than I normally would do you know how much air I had to move out of that well?
00:32:10.132 --> 00:32:12.432
In order to depressurize the Well.
00:32:12.731 --> 00:32:16.561
I do, you needed like 10 ccfm to properly capture that well.
00:32:16.561 --> 00:32:22.291
That's an additional 10 CFM that maybe the 15 you had in your other part of your system.
00:32:22.602 --> 00:32:23.352
It was higher flow.
00:32:23.352 --> 00:32:24.731
'cause we had 25 cfm.
00:32:25.031 --> 00:32:25.301
Yeah.
00:32:25.301 --> 00:32:26.622
Versus your normal 15.
00:32:26.622 --> 00:32:31.142
Where common systems in my area twin Cities area of Minnesota.
00:32:31.142 --> 00:32:34.682
We're talking probably 40 CFM, give or take 20 either way.
00:32:34.682 --> 00:32:38.811
If we see stuff much lower than that, it's gonna be on expansive or tight.
00:32:38.811 --> 00:32:40.521
Clay soils, wet soils.
00:32:40.521 --> 00:32:58.172
However more than that, then we're dealing with higher airflow contributors, whether it's string tile with weeper tile, weeper hoses from concrete block walls, or geologic foundations either KARST which is a fractured limestone bedrock, that some of our houses get built on.
00:32:58.172 --> 00:33:01.271
Or glacial moraine, where the glaciers came in.
00:33:01.271 --> 00:33:07.602
And this isn't just centric to Minnesota, but anywhere where the glaciers from Canada came, dropped a bunch of stones and then retreated.
00:33:07.602 --> 00:33:15.582
Then the top of the year, those stones got overlaid by top soil, but underneath you had got a big air void of caverns.
00:33:15.582 --> 00:33:23.801
If you're driving around where I live and work, somewhere underneath you are big old cobbles, bigger than my head, which is hard to believe by some people.
00:33:23.801 --> 00:33:29.402
The problem then is you have to deal with a whole lot of airflow in order to fix a radon problem in some cases.
00:33:29.402 --> 00:33:33.481
You also have to deal with mother nature, more so than you would in tight soils.
00:33:33.481 --> 00:33:39.192
An example I have is actually an entire subdivision built with radon resistant new construction features.
00:33:39.192 --> 00:33:42.491
House after house built in the subdivision are built on hills.
00:33:42.491 --> 00:33:44.922
There's hills and valleys within the subdivision.
00:33:44.922 --> 00:33:51.271
And had one really proactive homeowner who had, done a bunch of radon tests and week to week it would fluctuate.
00:33:51.271 --> 00:33:54.991
No matter the season, she could get a high result and she could get a low result.
00:33:54.991 --> 00:33:58.582
She called me in and I turned her basement into a laboratory.
00:33:58.582 --> 00:34:00.402
It's a fairly modern house.
00:34:00.402 --> 00:34:05.981
In Minnesota, we got pretty strict energy code requirements, our houses are built tight, but ventilated right.
00:34:05.981 --> 00:34:14.851
In this case, I could get the indoor pressure in the house to 20 Pascals negative just by turning on the exhaust fans.
00:34:14.851 --> 00:34:17.552
The building, the outside structure is quite tight.
00:34:17.552 --> 00:34:25.561
They come tighter than that, but in this case it was about 20 pascals where I can actually just by triggering the fans that are commonly using the house.
00:34:25.561 --> 00:34:27.211
That's gonna induce a radon problem.
00:34:27.376 --> 00:34:34.237
You're talking about you turned on the bathroom fans, the fans fan over the range in the kitchen, the dryer.
00:34:34.387 --> 00:34:34.536
Yep.
00:34:34.536 --> 00:34:40.777
So all the exhaust fans in the house went 20 Pascals negative relative to outside or relative to the soil?
00:34:41.126 --> 00:34:42.086
Relative to outside.
00:34:42.387 --> 00:34:43.677
That is insane.
00:34:43.677 --> 00:34:48.956
That's half a blower or test worth of negative pressure just by the exhaust fans.
00:34:49.257 --> 00:34:53.847
I've actually seen houses that can do their own blower door test without the blower door.
00:34:53.847 --> 00:34:59.007
But in this case this house had all the radon resistant features that are required by building code.
00:34:59.007 --> 00:35:06.146
It's got the gravel layer, the poly vapor barrier, and then a three inch vent stack up through the roof connected to the drain tile in this case.
00:35:06.416 --> 00:35:10.657
So they don't need they don't need to do a radon test because they have a radon system.
00:35:11.067 --> 00:35:11.916
Au contraire.
00:35:11.916 --> 00:35:18.117
In fact, I wish it's another, another topic for another podcast is testing newly constructed homes.
00:35:18.117 --> 00:35:18.896
We gotta do it.
00:35:19.197 --> 00:35:19.556
Yes.
00:35:19.836 --> 00:35:21.246
Homeowner's concerned.
00:35:21.246 --> 00:35:26.016
I get there, drill probably eight to 10 holes on the floor to get pressure field numbers.
00:35:26.016 --> 00:35:28.266
And the day I was there, everything was great.
00:35:28.266 --> 00:35:34.327
Negative pressure in all four corners and the half walls in between, or should say midpoint the walls in between.
00:35:34.327 --> 00:35:58.166
Everything looks good, except I know that at some point it's not gonna be good because the continuous radon data shows me that for two days, three days, it's fine and then all of a sudden, bam, it spikes, and I don't mean spikes to five or 10, I mean spikes to 150, for a handful of hours and then drops back down to what, let's call it background again, and then bam, it spikes again in another three or four days.
00:35:58.166 --> 00:36:02.907
So I'm checking this out and I'm also data logging side by side with the radon data.
00:36:02.907 --> 00:36:08.067
Every time the radon spikes, I'm losing my pressure field extension in certain parts of the basement.
00:36:08.067 --> 00:36:12.806
And not just losing it, like going from positive or negative five to positive five.
00:36:12.806 --> 00:36:16.077
I'm going from like negative 20 to Positive 70.
00:36:16.077 --> 00:36:16.617
What?
00:36:16.916 --> 00:36:17.277
Yes.
00:36:17.277 --> 00:36:18.146
70.
00:36:18.266 --> 00:36:18.867
That's pretty big.
00:36:18.867 --> 00:36:19.226
Yes.
00:36:19.226 --> 00:36:25.277
Hillside built house, and as the wind can suck and blow it can drive.
00:36:25.277 --> 00:36:27.226
I've measured these pressure changes.
00:36:27.226 --> 00:36:35.306
I've actually measured over time 150 Pascal pressure change just in one PFE location in a given home.
00:36:35.306 --> 00:36:41.677
We think we have robust systems installed, but we got nothing compared to what mother nature can throw at us sometimes.
00:36:41.681 --> 00:36:42.672
Just a second, Josh.
00:36:42.672 --> 00:36:48.632
Let's back up for a second because, you and I use Pascals for doing diagnostics in the floor.
00:36:48.632 --> 00:36:57.601
And there's a lot of people that will use inches of water column for diagnostics, or they don't do any diagnostics at all, and they just look at the U Tube manometer and they say, that's good enough.
00:36:57.601 --> 00:37:02.161
But 150 pascals would be like three quarters of an inch of water column.
00:37:02.161 --> 00:37:02.762
Right?
00:37:02.762 --> 00:37:07.202
You'd have to apply three quarters of an inch of water column to that spot.
00:37:07.202 --> 00:37:12.992
That's going 150 pascals positive in order to overcome that spike.
00:37:13.291 --> 00:37:13.862
That's right.
00:37:13.862 --> 00:37:20.972
So I've got an active construction system now that is getting overpowered by no mother nature.
00:37:20.972 --> 00:37:22.561
So what part of Mother Nature is it?
00:37:22.561 --> 00:37:35.371
I look at the wind from the local weather the weather stations, and I presented on this quite a few times, but you can, everywhere in the country, you can download the local climate data and you can see hour to hour weather data going back many years.
00:37:35.371 --> 00:37:38.612
As a weather dork, I know all this and I'm looking at it side by side.
00:37:38.612 --> 00:37:42.302
And it's not the wind or the wind direction that seems to be driving this.
00:37:42.302 --> 00:37:51.871
In this particular case, it's the atmospheric pressure and it's not the high pressure or the low pressure, it's when the pressure changes real drastically outside.
00:37:51.871 --> 00:37:55.771
So when storm fronts are rolling through and the barometric pressure is dropping.
00:37:55.771 --> 00:38:01.592
If it drops at a certain rate or worse, the radon will get sucked up by the atmosphere.
00:38:01.592 --> 00:38:17.876
It'll get sucked through the fairly hollow hillside and into these houses and at a clip that I cannot overcome with a three inch pipe, because the most airflow, I'm gonna move that three inch pipe, given the size of the pipe piping system is 60 or 70 CFM.
00:38:17.876 --> 00:38:18.836
Oh, come on, Josh.
00:38:18.836 --> 00:38:21.476
The fans are rated for 250 c fm.
00:38:21.476 --> 00:38:25.407
I know, but there's bottlenecks in these pipes, so I can't move anymore.
00:38:25.407 --> 00:38:33.836
So the solution here, given the criteria of multimillion dollar house, not gonna put a whole bunch of bigger pipes in all over.
00:38:33.836 --> 00:38:40.947
They switched from one three inch stack to two four inch stacks, and then a higher airflow fan.
00:38:40.947 --> 00:38:53.726
And I dropped the spikes from 120 for four to six hours, to now it spikes to maybe 10 picocuries for four to six hours when these super aggressive, low pressure centers roll through.
00:38:53.726 --> 00:38:55.916
But it's only in this correct case.
00:38:55.916 --> 00:39:03.476
I could predict when the radon would get super high without seeing the tape, just by looking at the atmospheric pressure trend over the last three days.
00:39:03.476 --> 00:39:09.442
If it dropped more than four milli bars over six hours, I'm gonna get a super high radon level.
00:39:09.442 --> 00:39:15.742
But if it just gradually drops, four millibars over 12 hours, the radon system can can actually handle that.
00:39:15.742 --> 00:39:21.532
So it's like the, kinda like a tsunami of air coming at that house, or the tsunami of radon coming at that house.
00:39:21.532 --> 00:39:26.032
If it all comes at once, I can't control it, but if it gradually comes, I can.
00:39:26.032 --> 00:39:27.351
But you're not gonna know that.
00:39:27.351 --> 00:39:33.052
Unless you're actually there or have something there to monitor the pressure or the radon all of the time.
00:39:33.351 --> 00:39:34.342
Josh, quick question.
00:39:34.342 --> 00:39:41.211
Going back, does your measurement device also measure barometric pressure and temperature or do you have specific devices for those measurements?
00:39:41.681 --> 00:39:44.231
I don't have specific devices for those measurements.
00:39:44.231 --> 00:39:46.811
Some continuous monitors do measure those things.
00:39:46.811 --> 00:39:52.001
I honestly don't put a lot of, credence in those numbers 'cause I just never double check them.
00:39:52.001 --> 00:39:58.541
And they're measuring atmospheric pressure and temperature in the device, not outside, which is actually more important.
00:39:58.541 --> 00:40:02.501
The temperature difference between inside and outside is more important than the temperature in the basement.
00:40:02.501 --> 00:40:10.452
And likewise they may be measuring atmospheric pressure in inches of mercury, which is a whole different ballgame than actually milli bars.
00:40:10.452 --> 00:40:18.161
Probably a more sophisticated device, which is why we rely on the weather service stuff that actually measured and verified rather than what's coming outta the monitors.
00:40:18.161 --> 00:40:22.152
But even if you were to look at if the monitor, some monitors will track that over time.
00:40:22.152 --> 00:40:24.942
You can see that at a sharp barometric pressure drop.
00:40:24.942 --> 00:40:31.197
If you're had a high airflow situation, you will see sometimes a spike in the amount of radon.
00:40:31.197 --> 00:40:32.882
And it works in inverse as well.
00:40:32.882 --> 00:40:41.461
So when the pressure rises really fast outside, that's the atmosphere, pushing the air back into the hillside and thereby pushing the radon out of the house.
00:40:41.461 --> 00:40:42.811
So you can see that too,
00:40:42.822 --> 00:40:47.681
I think this is interesting because it's something that we don't see very often.
00:40:47.681 --> 00:40:52.541
We don't see the atmospheric pressure spikes because we don't have a lot of available air in the soil.
00:40:52.541 --> 00:40:57.822
Now I always think of this situation where my kids and I were going skiing up in the.
00:40:57.822 --> 00:41:17.411
Colorado Mountains one year, and we're driving up this pass, it goes up to 10,000 feet and there's this chip bag in the back of the car where the kids are sitting and they're like, oh my goodness, this chip bag is going to explode because there's less atmosphere above, above us when we're going up the pass.
00:41:17.411 --> 00:41:20.592
The exact same thing is happening when the atmospheric pressure drops.
00:41:20.592 --> 00:41:25.132
It is going to expand that chip bag, not as much as driving up a mountain pass, right?
00:41:25.132 --> 00:41:28.492
But the air inside the hillside is wanting to expand.
00:41:28.492 --> 00:41:34.072
If the preferential pathway is into the house, where's that air going to go into the house?
00:41:34.077 --> 00:41:34.197
Makes sense.
00:41:34.347 --> 00:41:35.876
To finish a story about the chip bag.
00:41:35.876 --> 00:41:37.677
It did explode in the back of my car.
00:41:37.677 --> 00:41:44.606
I was hoping for chips to go everywhere you know, just like be this big explosion that just kind of popped and it was not very exciting.
00:41:44.606 --> 00:41:45.206
Not as dramatic.
00:41:45.416 --> 00:41:45.867
No.
00:41:45.867 --> 00:41:53.177
But if we took all of the air out of that chip bag before we went over the mountain pass, there just wouldn't be as much air to expand.
00:41:53.177 --> 00:41:59.536
If we had a vacuum sealed bag going over the of the mountain pass, it's not going to expand enough to be super visible.
00:41:59.536 --> 00:42:07.726
And that's what happens where we're at here in the middle of Kansas and most of the plane states, because we're working in really tight soils that don't have a lot of available air.
00:42:07.726 --> 00:42:14.177
We don't see that spike as commonly as you would in Minnesota or somewhere that has glacial Moraine or KARST geology.
00:42:14.527 --> 00:42:17.106
And KARST is actually more prevalent than a lot of people think.
00:42:17.106 --> 00:42:18.547
If you're on a river bluff.
00:42:18.547 --> 00:42:21.666
You're gonna have dissolved bedrock nearby, typically.
00:42:21.666 --> 00:42:24.547
So there are rivers in all of our states.
00:42:24.547 --> 00:42:29.226
We've got somewhere, you're gonna have higher air flows in small geographic locations.
00:42:29.226 --> 00:42:31.717
It's not completely homogenous everywhere in Kansas.
00:42:31.717 --> 00:42:34.237
But, a lot of Kansas is how Chad described it.
00:42:34.237 --> 00:42:43.536
But you're gonna have glacial Moraine and KARST in a lot of the upper Midwest, basically anything east of the Mississippi and say Tennessee North, you're gonna find a lot of it.
00:42:43.737 --> 00:42:45.086
There's KARST in Alabama.
00:42:45.436 --> 00:42:46.936
The Appalachians as well too.
00:42:46.936 --> 00:42:48.376
It's more prevalent than you think.
00:42:48.806 --> 00:42:56.547
We have KARST, geology in Manhattan Kansas South down through EL Dorado or somewhere in there that's the, what we call the Flint Hills.
00:42:56.547 --> 00:42:57.536
There's KARST there.
00:42:57.536 --> 00:43:02.956
I've worked on the edges of that geology in a different house that we had a well problem in.
00:43:02.956 --> 00:43:06.586
We did have a atmospheric pressure burp of radon into the house.
00:43:06.586 --> 00:43:22.487
But that had 175 foot deep well that went into one of those layers that had some openings in the soil, but typically close to the surface around us in the Flint Hills, there's clay packed into all the limestone in those hills.
00:43:22.487 --> 00:43:28.456
It's still pretty tight soils, but if you go deep enough, you can find some openings even in Kansas.
00:43:28.757 --> 00:43:29.117
Wow.
00:43:29.117 --> 00:43:29.686
That's great.
00:43:29.686 --> 00:43:42.056
We could go on and on about with these stories because they're really interesting and certainly these examples today have been pretty I would assume unique, but still just they're there and something for all of us to be aware of.
00:43:42.056 --> 00:43:46.909
As we close out here guys what would you say one common myth about tough mitigation is?
00:43:46.909 --> 00:43:47.869
What would you say to that?
00:43:48.170 --> 00:43:49.670
I have enough experience.
00:43:49.670 --> 00:43:53.119
I know what I'm doing, but I'm not doing pressure field extension.
00:43:53.119 --> 00:43:55.010
That's a common thing I hear.
00:43:55.010 --> 00:44:00.269
My experience tells me that I don't need to worry about radon on X location, and I ask, WHY?
00:44:00.269 --> 00:44:01.510
verify it.
00:44:01.510 --> 00:44:06.519
Too many contractors are not doing pressure field extension work, and that's really hurting the industry.
00:44:06.519 --> 00:44:15.309
Frankly! If everyone was doing pressure field extension work and understood what the numbers actually mean we would have far fewer system failures.
00:44:15.309 --> 00:44:22.599
We'd have far fewer oversized radon systems, costing millions more dollars to operate than we'd need.
00:44:22.599 --> 00:44:24.280
That's my biggest problem.
00:44:24.480 --> 00:44:30.449
The noise issue associated with larger oversized systems is a big concern.
00:44:30.449 --> 00:44:39.510
When I started, in the radon business, I was talking to a realtor at a house and she had to answer the phone and she said something about 'em here with the radon guy.
00:44:39.510 --> 00:44:43.210
The next thing I hear her say is, yeah, they're loud sometimes, but you get used to it.
00:44:43.210 --> 00:44:49.840
And I'm like, oh, if that's what people think, I'm gonna figure out a way to make sure that we don't have loud systems.
00:44:49.840 --> 00:44:57.295
It's very uncommon in houses that we need radon fan that's loud enough that it's gonna cause problems.
00:44:57.295 --> 00:44:59.175
They shouldn't have to get used to it.
00:44:59.175 --> 00:45:07.625
The common thing that I hear people say is if you still have high radon levels, you just need to move more air, put a bigger fan on and move more air.
00:45:07.625 --> 00:45:17.164
In the case that I talked about at Skipper, would moving more air have helped if it was in a random location or in the suction point that we already had in place?
00:45:17.164 --> 00:45:18.034
Absolutely not.
00:45:18.034 --> 00:45:25.985
And if we would've put a suction point in every corner of that basement and in the patios and in the garage, it would've done absolutely no good.
00:45:25.985 --> 00:45:27.335
Just moving more air.
00:45:27.614 --> 00:45:28.664
Go through what you had to go through.
00:45:28.664 --> 00:45:32.715
And it's, it's not necessarily always easy, you know, from your experience.
00:45:32.715 --> 00:45:40.394
Certainly, you all professionals do have that to draw from, but these examples, sometimes it takes a little extra time and a little extra work.
00:45:40.394 --> 00:45:41.114
It does.
00:45:41.114 --> 00:45:44.445
And the contractors shouldn't be running scared from these things.
00:45:44.445 --> 00:45:47.534
In fact, as a director, maybe you could have some input on this.
00:45:47.534 --> 00:45:52.605
The best experience some a contractor will get is just keeping with these difficult houses.
00:45:52.605 --> 00:45:56.224
And they'll get that experience and it's better than any CE class that they'll ever take.
00:45:56.224 --> 00:46:02.434
So if they can somehow come up with a presentation or paper, maybe you could award some additional CEs from your credentialing body.
00:46:02.434 --> 00:46:17.389
One other thing that I wanna really stress is there's a common misnomer nationwide, worldwide, frankly, where you pop a hole on a foundation and you see what type of soil is there that shall dictate the type of radon fan you use.
00:46:17.389 --> 00:46:18.949
And that is simply untrue.
00:46:18.949 --> 00:46:25.880
Just because Chad runs into clay soils does not mean he uses high suction radon fans.
00:46:25.880 --> 00:46:36.920
High suction radon fans are expensive to start with and they're loud, and just by him sucking harder in the north corner of a basement doesn't mean he's going to get better PFE in the south corner.
00:46:36.920 --> 00:46:49.920
The better way to get PFE in that south corner is a second suction point and using a smaller radon fan, if that piece of intellect was industry wide, we would be so much better.
00:46:49.920 --> 00:46:57.300
The substrate should not dictate the type of fan you use your numbers from your PFE analysis should dictate that fan you use.
00:46:57.599 --> 00:46:58.135
Great information.
00:46:58.184 --> 00:47:04.485
The thing that i've heard w ay too often people say, I look at my u tube when I'm done putting the radon system in.
00:47:04.485 --> 00:47:10.635
And if it's below a certain amount, then I feel pretty confident that we're gonna fix the radon problem in this house.
00:47:10.635 --> 00:47:14.804
That might be lower just because you have a bunch of pipe above the fan.
00:47:14.804 --> 00:47:19.454
Because if you have resistance above the fan, the differential is going to go down.
00:47:19.454 --> 00:47:23.425
That is not an indicator of success.
00:47:23.425 --> 00:47:35.635
I don't know where people get that idea that, oh, hey, we have to have our U Tube be below 1.8 or 1.5 or something like that with a mid-range fan to have success.
00:47:35.635 --> 00:47:37.114
It's not about that at all.
00:47:37.114 --> 00:47:44.590
Can we measure the pressures in the floor everywhere and do we have negative pressures in the floor relative to inside the house?
00:47:44.590 --> 00:47:46.570
Chad, to wrap up, you live in clay country.
00:47:46.570 --> 00:47:47.769
You work in clay country.
00:47:47.769 --> 00:47:52.360
When was the last time you used a high suction fan in a single family residence?
00:47:52.659 --> 00:47:59.659
I've been in the radon business for over 15 years, and it was probably 12 or 13 years ago, maybe longer than that.
00:47:59.659 --> 00:48:04.900
So the common notion would say that you should be running high suction fans every job, and you simply don't.
00:48:04.900 --> 00:48:05.829
Because you know better.
00:48:05.829 --> 00:48:12.360
And actually, if we have a good preferential pathways in the soil, we use low pressure fans.
00:48:12.710 --> 00:48:15.590
Meaning low flow or low wattage fans.
00:48:15.590 --> 00:48:16.010
Right?
00:48:16.014 --> 00:48:26.934
A low wattage fan, like a RN one Spirit or RP one 40, that we use those 30 to 40% of the time in clay soils.
00:48:27.235 --> 00:48:27.385
Huh.
00:48:27.385 --> 00:48:27.835
Wow.
00:48:27.835 --> 00:48:36.235
Josh, Chad, thank you both for being here and for kicking off this podcast, the stories that are both surprising and really insightful.
00:48:36.235 --> 00:48:46.590
If you wanna carry on this conversation with Chad and Josh, please join us in Fort Worth this year, in October, we will, be meeting for our annual radon and VI symposium.
00:48:46.590 --> 00:48:48.599
Should be a really informative and fun event.
00:48:48.599 --> 00:48:52.260
So check out our website to get more information on that.
00:48:52.260 --> 00:48:57.449
For our listeners, if this episode made you nod your head or laugh a little, don't forget to subscribe.
00:48:57.449 --> 00:49:01.079
Share it with your team and send us your house from Heck Stories.
00:49:01.079 --> 00:49:03.449
We might feature one on a future episode.
00:49:03.449 --> 00:49:05.610
Breathe easy and keep doing the good work.
00:49:05.610 --> 00:49:07.206
Thanks! Take care everyone.
00:49:07.963 --> 00:49:10.780
That’s it for this episode of The Indoor Environment Project.
00:49:10.780 --> 00:49:19.554
If you enjoyed the conversation, learned something new, or just felt seen by the stories—we’d love it if you subscribed, shared this episode with your team, or left us a review.
00:49:19.554 --> 00:49:20.730
Want to go deeper?
00:49:20.730 --> 00:49:26.505
Join the Indoor Environments Association and be part of the movement to improve the spaces we live and the air we breathe.
00:49:26.505 --> 00:49:33.054
Membership gives you access to a national network of pros, discounts, standards, CE courses, and so much more.
00:49:33.054 --> 00:49:35.800
Visit indoorenvironments.org to join today.
00:49:35.800 --> 00:49:44.050
And don’t forget to follow us on social media for updates, insights, and real-world stories from the field—we're on LinkedIn, Instagram, and Facebook.