Uh what I see is a very simple recipe for success is make sure they're installed properly, protect them against extreme duty cycle, and let them go.
00:00:18.559 --> 00:00:23.120
How do installation practices impact the long-term reliability of cables?
00:00:28.079 --> 00:00:37.439
Installation practices are really the key to longevity because the vast majority of anomalies in cable systems exist from day one.
00:00:37.679 --> 00:00:42.079
And the majority of those anomalies are installation issues.
00:00:42.399 --> 00:00:48.960
Human contact with cable systems is by far the biggest risk factor to future failure.
00:00:49.039 --> 00:00:56.399
So everything, in fact, we really want to focus on the quality of new installations to prevent future outages.
00:00:56.640 --> 00:01:08.400
And uh there's many reasons for that, but one in particular is the fact that as an aged cable, say about five to ten years into service, it's ten times more likely to fail a second time if it's failed once.
00:01:08.560 --> 00:01:17.280
So we really want to prevent all of that future escalation and exponential growth of failures by focusing on the beginning of the life of a cable system.
00:01:20.480 --> 00:01:24.400
Can you discuss the role of environmental conditions in cable degradation?
00:01:27.599 --> 00:01:33.280
Yeah, so environmental conditions, many people misunderstand how cable systems fail.
00:01:33.519 --> 00:01:41.920
So when we're looking at uh low voltage cable systems, uh the predominant failure mechanism is just mechanical damage.
00:01:42.879 --> 00:01:54.959
When we talk about medium and high voltage cable systems are which are more coaxial in structure, uh there's multiple layers of a ground layer on the outside and a conductor in the middle.
00:01:55.280 --> 00:02:05.120
Uh once you get over about, well, say 5,000 volts and higher, 5 kV class and higher, the world changes and the failure mechanism is completely different.
00:02:05.200 --> 00:02:18.159
So while at low voltage, say less than 1,000 volts, the primary failure mechanism is just mechanical damage and then uh leakage currents through uh conduction.
00:02:18.479 --> 00:02:29.439
Um and if it's an aluminum conductor, it actually oxidizes the aluminum and it becomes more and more of an open circuit over time and eventually you have brownouts and eventually open circuit.
00:02:29.599 --> 00:02:33.520
That's more on the utility side, mostly the industrial side, a lot of copper cable.
00:02:33.680 --> 00:02:42.479
But when it comes to medium and high voltage cable systems, the the failure mechanism is associated with what we call partial discharge.
00:02:42.560 --> 00:02:48.159
It's a micro erosion or micro arcing process that erodes insulation over time.
00:02:48.400 --> 00:02:51.120
And it's not a continuous erosion process.
00:02:51.199 --> 00:02:57.280
In the vast majority of cases for modern cable systems, it's an intermittent erosion process.
00:02:57.439 --> 00:03:10.159
So it's not growing all the time, it only grows during uh extreme environmental, or you could call it environmental conditions, but it's not say the moisture in the ground or something like that.
00:03:10.319 --> 00:03:23.520
It's actually uh the extreme voltage, so transients, microsecond to millisecond bursts of voltage uh that occur every day on power systems that turn the defect on and turn it off, turn on, turn off.
00:03:23.680 --> 00:03:34.879
And over time, that erosion, that intermittent erosion, uh will eat through all the material and eventually cause partial discharge uh continuous at the operating voltage and then eventual failure.
00:03:37.919 --> 00:03:42.319
Can you share examples where predictive maintenance has prevented potential failures?
00:03:45.759 --> 00:03:46.800
Well, for sure.
00:03:46.879 --> 00:03:59.120
Uh there's many great case studies that show that if we can identify where these defects are and protect the system against extreme operating conditions.
00:03:59.439 --> 00:04:06.240
So we can we can extend the life two to three times, uh what most people would say 30 to 40 years.
00:04:06.479 --> 00:04:15.439
The reality is cable systems can last longer than 100 years if, again, we remove those defects, primarily those issues that existed from day one.
00:04:16.000 --> 00:04:19.439
And ideally, we would get those out of the system from day one.
00:04:19.680 --> 00:04:30.000
However, if we didn't do that with an effective uh technology to scan the asset, we can do that scan later in life.
00:04:30.079 --> 00:04:39.040
Uh that scan in particular has a detailed specification, what we call an offline 50 or 60 hertz partial discharge test with 5 PC sensitivity.
00:04:39.199 --> 00:04:51.120
That is a direct comparison to the cable and accessory manufacturer's quality control standard that they use for all uh production and design testing.
00:04:51.279 --> 00:05:17.920
So if we can repeat that process in the field on a meter by meter, foot by foot basis and find these issues that are substandard, and then once we remove those defects, protect the system against extreme conditions, primarily voltage, extreme voltage, which means you put surgery arrestors on the system, and then secondarily uh protect them against extreme loading, both of which we can control through design and operation practices.
00:05:19.360 --> 00:05:24.800
What are the most common failure modes observed in high and medium voltage power cables?
00:05:26.720 --> 00:05:41.360
Yeah, the most common uh failure modes for medium and high voltage cable systems, uh, as I mentioned earlier, are associated with partial discharge and they are virtually mechanical damage, usually at a very small level.
00:05:41.519 --> 00:05:52.800
We're talking about a few mils, very uh small, sometimes difficult to see, but definitely still in the visual range of defects that occur in the joints and terminations.
00:05:54.319 --> 00:06:03.759
It's
Load full transcript
about 1% of cable system segments, about 4% of splices, and 4% of terminations that get installed incorrectly from day one.
00:06:04.000 --> 00:06:17.360
And if you look at statistically, just about 40% of new installs will have at least one substandard component, meaning the component no longer meets the minimum expected performance that where it as it left the factory.
00:06:17.519 --> 00:06:22.480
So some of us have damaged it along the way, shipping, handling, installing.
00:06:23.040 --> 00:06:26.560
And this is what is damaging cable systems.
00:06:26.720 --> 00:06:39.920
Now, there are things that can happen over time to the cable, but the vast majority of the first failure in a system is caused most often by a defect that existed from day one.
00:06:40.160 --> 00:06:58.879
Uh but there are, let's just say, phenomena that can happen over time, but those are usually only derived, or they're the the origin story of even defects that can grow over time most often have this origin story from day one.
00:06:58.959 --> 00:07:08.800
So, really, that's what we want to focus on the existing defects uh that are caused by either manufacturing process or human interaction from day one.
00:07:12.160 --> 00:07:14.639
Water trees one of those silent killers.
00:07:14.800 --> 00:07:15.920
How does it form?
00:07:16.000 --> 00:07:18.240
And how long can it go unnoticed?
00:07:20.959 --> 00:07:36.319
Yeah, well, water trees are perhaps one of if someone studies cable at medium and high voltage cables, it's almost impossible not to see water trees mentioned in so-called degradation mechanisms.
00:07:36.480 --> 00:07:39.519
And the reality is water doesn't fail cable.
00:07:39.680 --> 00:07:41.680
Water trees don't fail cable.
00:07:41.839 --> 00:07:45.839
Uh, it's a phenomenon called electrical treeing that actually fails the cable.
00:07:46.000 --> 00:07:51.839
Water trees, the only way you get a water tree is if there's an existing anomaly.
00:07:52.079 --> 00:07:57.439
See, water is a polar molecule and it's attracted to higher electric stress.
00:07:57.600 --> 00:08:07.519
So if I have a manufacturing, a manufacturer's defect in the system that creates a little higher stress in a certain area, it'll draw the water molecule to it.
00:08:07.680 --> 00:08:14.879
And then as the electric field is distributed throughout that insulation, it it draws a higher concentration of moisture to that area.
00:08:14.959 --> 00:08:27.519
And when you have a wet, dry interface, so an area of high moisture and an area of low moisture, you get a higher stress in the drier part of the insulation.
00:08:27.759 --> 00:08:57.440
And when that happens, if by chance a perfect storm scenario where you have this plume of moisture inside the cable insulation, originally caused by a stress enhancement from a manufacturing defect, when you have the stress, higher stress in that dry part, if there happens to be a secondary manufacturing defect, so perfect storm scenario, in that location, you can achieve stresses in that 10 to 12 kb per millimeter range, which is where you can create new defects.
00:08:57.679 --> 00:09:09.039
So, under transient conditions, if you have this little dry area of the insulation that's taking all the stress, now you have the scenario, this perfect scenario to create a new defects called an electrical tree.
00:09:09.120 --> 00:09:11.759
And the electrical tree will grow intermittently.
00:09:12.399 --> 00:09:22.080
Uh, and it actually takes uh a very long time mostly uh to fail because again, it's only growing when a microsecond or millisecond transient occurs.
00:09:22.240 --> 00:09:47.039
So, this whole idea of water treeing, there are trillions and trillions of water trees out there in every age cable that I've ever dissected, and I've dissected many, and we've um I've had the privilege of not only not only overseeing hundreds of thousands of cable assessments on new and aged aged systems, but also thousands of dissections.
00:09:47.200 --> 00:09:54.799
Um, and I can tell you, I have yet to extract an aged cable that didn't have water treeing in it.
00:09:54.960 --> 00:09:59.120
So, water trees are not the problem, and random moisture is not the problem.
00:09:59.200 --> 00:10:07.200
It's concentrated moisture in this unique scenario, and the likelihood of that happening is actually quite rare.
00:10:07.440 --> 00:10:15.919
And if we address the quality control process in the beginning of the life of the asset, these water trees generally are not an issue.
00:10:16.159 --> 00:10:24.320
So uh it is part of the story, but like every good myth, there's some truth and a lot of confusion.
00:10:24.480 --> 00:10:53.440
And as it relates, if we can very use this very simple recipe, scan these systems from day one, make sure that they're installed correctly, and then protect them against extreme duty cycle, and perhaps throw a couple more specifications into a cable systems design, such as shear bolt connectors to prevent poor connections and eliminating, say, constant force springs on the shields over a uh over a splice.
00:10:53.679 --> 00:11:12.159
A couple things like this, if we can tune the specification up on the design side, commission it, make sure it doesn't have defects, fix all those issues, and then protect it against extreme duty cycle, there's no reason why these assets uh shouldn't last uh an 80, 90, 100 years.
00:11:12.480 --> 00:11:23.759
And ultimately, uh what I see is a very simple recipe for success is make sure they're installed properly, protect them against extreme duty cycle, and let them go.
00:11:23.919 --> 00:11:26.639
You shouldn't have to touch that asset at least for 20 years.
00:11:26.799 --> 00:11:30.639
So this taking it out every couple years to see if it's still good is ridiculous.
00:11:30.960 --> 00:11:36.399
Unless we have an extreme duty cycle scenario, which in many cases we know.
00:11:36.639 --> 00:11:40.399
If there was an arrestor that failed, obviously the voltage was too high.
00:11:40.639 --> 00:11:42.799
Now we probably should re-baseline that asset.
00:11:42.960 --> 00:11:46.240
If you've overloaded the system, now it's time to take another look.
00:11:46.320 --> 00:11:50.000
But those are clear indications of when we need to take another look.
00:11:50.159 --> 00:11:56.240
And the idea of just continual looking at assets uh is really a waste of time.