TRASCRIZIONE 🔗
WEBVTT
00:00:01.600 --> 00:00:06.000
Welcome to the Ask Caleffi Podcast coming at you live from the lab.
00:00:06.000 --> 00:00:07.919
Guys, what do we got going on?
00:00:07.919 --> 00:00:13.279
Plumbing, hydronics, expert insights, and a few stories from the trenches.
00:00:13.279 --> 00:00:18.399
Whether you're on the job or just along for the ride, we've got you covered.
00:00:22.640 --> 00:00:26.719
Hey there, welcome back to another episode of the Ask Caleffi Podcast.
00:00:26.719 --> 00:00:31.519
We're here hanging out in the lab, gonna talk a little bit about separation.
00:00:31.519 --> 00:00:34.320
Separation's a pretty broad term, would you not say?
00:00:34.320 --> 00:00:36.240
I mean, there's multiple ways of separating.
00:00:36.240 --> 00:00:38.719
A lot of different types of separation options there.
00:00:38.719 --> 00:00:40.320
We got to keep them separated.
00:00:40.320 --> 00:00:41.200
Absolutely.
00:00:41.200 --> 00:00:42.560
Keep us separated.
00:00:42.560 --> 00:00:44.719
No, they can't keep us separated.
00:00:44.719 --> 00:00:45.840
That's why we're all here.
00:00:45.840 --> 00:00:49.679
Um, we got a few different options here on the table, don't we?
00:00:49.679 --> 00:00:55.439
I mean, we've got an air separator, which we know air in hydronic systems is terrible.
00:00:55.600 --> 00:00:55.759
Right.
00:00:55.920 --> 00:00:56.159
Right?
00:00:56.159 --> 00:00:56.479
Yep.
00:00:56.479 --> 00:01:05.519
Got to get rid of it so we can actually conduct heat and uh and get fluid movement through the system because we know that circulators don't move air very well.
00:01:05.519 --> 00:01:07.760
Also help keep the system clean.
00:01:07.760 --> 00:01:08.879
Exactly.
00:01:08.879 --> 00:01:12.159
Um, dirt separators, right?
00:01:12.159 --> 00:01:14.000
Keep the debris out of boilers.
00:01:14.000 --> 00:01:21.920
You get a an existing system that maybe had old cast iron boiler in it, has cast iron rads, or just a mix of different piping and different materials.
00:01:21.920 --> 00:01:27.120
It does break down over time, creates rust, um, ferrous material, things like that.
00:01:27.760 --> 00:01:37.359
You need a dirt separator in there to protect high efficiency boilers that you're gonna put in, especially with those new heat exchangers, high efficient heat exchangers, small little ports in them.
00:01:37.359 --> 00:01:39.280
Yep, tidy little passageways.
00:01:39.280 --> 00:01:39.920
Yes, exactly.
00:01:40.159 --> 00:01:40.959
Oh, you're up in a hurry.
00:01:41.040 --> 00:01:41.599
Yeah, they do.
00:01:41.599 --> 00:01:42.079
Yeah.
00:01:42.079 --> 00:01:45.599
Then we have that little monster over there.
00:01:45.599 --> 00:01:51.519
Um, the air dirt separator, which uh that it's always a hot topic of debate.
00:01:51.519 --> 00:01:52.480
What should I use?
00:01:52.480 --> 00:01:53.920
Should I use an air?
00:01:53.920 --> 00:01:55.280
Should I use an air dirt?
00:01:55.280 --> 00:01:56.480
Should I use a dirt?
00:01:56.480
Load full transcript
--> 00:01:58.560
The answer is yes to all of that.
00:01:58.560 --> 00:02:05.280
Uh, but the air dirt has more of a a niche area where we would like to see it, in my opinion.
00:02:05.280 --> 00:02:10.719
I mean, maybe you guys have a different opinion of it, but I'll explain my stance on it in a few minutes.
00:02:10.719 --> 00:02:14.639
Then over here we have a hydraulic separator.
00:02:14.639 --> 00:02:25.120
Actually, it's our set four, which allows you to do hydraulic separations, so pump decoupling to prevent any kind of uh, you know, conflict of pump.
00:02:25.680 --> 00:02:28.319
Yeah, pump conflict across the two sides of the system.
00:02:28.560 --> 00:02:28.960
Yep.
00:02:28.960 --> 00:02:29.520
Right.
00:02:29.520 --> 00:02:39.199
You have an air coalescing mesh on top, a really nice air vent on the top, and then you have coalescing mesh in the bottom with a magnet that helps catch any of the ferrous material.
00:02:39.199 --> 00:02:41.840
So we're doing four different things there.
00:02:41.840 --> 00:02:44.639
And then a place to bleed it off to.
00:02:45.680 --> 00:02:47.439
Yeah, so you highlighted our CEP4.
00:02:47.439 --> 00:02:51.039
Um, we're gonna have two options in the hydraulic separators.
00:02:51.039 --> 00:02:55.120
We'll have just our 548 series, which is standard hydraulic separation.
00:02:55.120 --> 00:03:02.479
You know, you may get some air and dirt removal as a you know, byproduct of that velocity drop, but not designed to separate air and dirt.
00:03:02.479 --> 00:03:03.120
Yeah.
00:03:03.120 --> 00:03:03.840
Right.
00:03:03.840 --> 00:03:07.840
And I mean, if if I'm picking, I'm getting the SEP4.
00:03:07.840 --> 00:03:10.000
Because it's it it's four and one.
00:03:10.000 --> 00:03:10.639
It's everything.
00:03:10.639 --> 00:03:10.879
Right.
00:03:10.879 --> 00:03:13.280
It's uh why add any more components?
00:03:13.280 --> 00:03:17.199
You can put the one product in and walk away.
00:03:17.199 --> 00:03:18.479
Yeah, you're exactly right.
00:03:18.479 --> 00:03:20.800
I mean, I talked about the hydraulic separator.
00:03:20.800 --> 00:03:27.599
You know, that's gonna provide hydraulic separator separation, but you're still gonna need air to add air and dirt separation.
00:03:27.599 --> 00:03:28.000
Right.
00:03:28.000 --> 00:03:32.000
Where you're right, right here with four connection points, you have all of that in one.
00:03:32.000 --> 00:03:32.960
Exactly.
00:03:33.199 --> 00:03:33.919
Exactly.
00:03:33.919 --> 00:03:36.240
It takes away a lot of guesswork.
00:03:36.240 --> 00:03:57.919
And if we can just kind of keep beating the hydraulic separation drum here, um if we were to do closely spaced T's, if they're not done correctly, if they're not spaced correctly, um, you know, before and after a set of elbows, distance between the T's, not generously sized, you're gonna run into all sorts of issues, right?
00:03:57.919 --> 00:03:59.280
Yeah, you'll get pump conflict.
00:03:59.520 --> 00:04:00.800
Yep, it's not gonna work.
00:04:00.800 --> 00:04:05.120
This is pre-designed, pre-engineered, it's kind of plug and play.
00:04:05.280 --> 00:04:08.400
Yeah, and there's no minimum distances from elbows.
00:04:08.400 --> 00:04:13.120
Um, you can come in with an elbow, a street elbow if you wanted to.
00:04:13.120 --> 00:04:15.520
Um street elbow in, street elbow out.
00:04:15.520 --> 00:04:21.279
Um it makes it a really simple um it saves room, saves connections.
00:04:21.279 --> 00:04:28.399
You know, if we were to do the math, if we're doing an air and dirt separator and we're doing the the closely space tease, that's that's 10 connections.
00:04:28.399 --> 00:04:28.879
Right.
00:04:29.120 --> 00:04:35.920
And that's probably the biggest question I get is how far or how long does the pipe have to be coming off of it?
00:04:35.920 --> 00:04:36.480
Nothing.
00:04:36.480 --> 00:04:36.959
Nothing.
00:04:36.959 --> 00:04:41.600
I mean, you could put four street 90s right into this thing, and you're good to go.
00:04:41.759 --> 00:04:44.160
And they and people want to know, well, why is that?
00:04:44.160 --> 00:04:45.199
Why is that the case?
00:04:45.199 --> 00:04:50.959
Why do we not need a piece of straight pipe for laminar flow like we would on a Takeover or whatever air scoop, right?
00:04:50.959 --> 00:04:51.680
Right.
00:04:51.680 --> 00:04:55.600
Because we have a very wide barrel there.
00:04:55.600 --> 00:04:58.639
It's usually a three to one difference from the connection size.
00:04:58.639 --> 00:05:02.319
So if it's one inch coming in, it's a three-inch barrel or better.
00:05:02.319 --> 00:05:02.720
Right.
00:05:02.720 --> 00:05:13.120
So you have a reduction in velocity and the fact that we have coalescing mesh there, no matter where the bubbles are, if they're in the bottom of the pipe or the side or the top, it's always going to be able to grab those bubbles.
00:05:13.120 --> 00:05:18.160
It gives a surface to for them bubbles to cling to where an air scoop, there's nothing in there.
00:05:18.160 --> 00:05:35.360
There's a couple of little little veins that if you're lucky, most of the bigger bubbles due to gravity and reduced velocity, provided you have that 18 inches of straight pipe, right, to make it laminar gives it a chance to come out of the elbow and you know, float up and kind of hug the top of the pipe.
00:05:35.360 --> 00:05:36.800
You don't have to worry about that with this.
00:05:36.800 --> 00:05:37.519
Right, right.
00:05:37.680 --> 00:05:40.639
And I mean, a lot of guys that go, well, it's kind of big.
00:05:40.639 --> 00:05:42.079
How do I get it into a system?
00:05:42.079 --> 00:05:43.600
We got a tight, tight area.
00:05:43.600 --> 00:05:48.240
Well, you can go right off with street 90s, street 45s, whatever you need.
00:05:48.240 --> 00:06:04.399
Well, and you're right, it is larger, but when you start looking at using closed space T's and all the connection by the time you're doing it, you need and and straight
lengths of pipe, um, and then adding in dirt separator and an air separator on top of that, you you you're starting to grow the footprint of that system.
00:06:04.399 --> 00:06:14.800
I mean, I I think when you look at it from that point, to be able to come right out of your boilers into one side, out of the other side to your system and have that four-in-one protection, it probably ends up taking up less space.
00:06:14.800 --> 00:06:16.959
It does, it saves wall space for sure.
00:06:16.959 --> 00:06:18.399
Wall space and time.
00:06:18.399 --> 00:06:18.720
Yeah.
00:06:18.720 --> 00:06:19.839
Definitely.
00:06:20.079 --> 00:06:21.839
It's it's a win-win all the way around.
00:06:21.839 --> 00:06:24.639
So, you know, look at what your labor is worth.
00:06:24.639 --> 00:06:30.399
If you took the time, if you're a solder guy still even press, I mean, that's more press joints.
00:06:30.399 --> 00:06:37.120
And if something got messed up with uh with your press in closely spaced tees, now you gotta cut all that out.
00:06:37.279 --> 00:06:37.600
Yeah.
00:06:37.600 --> 00:06:40.160
I mean, and we're showing our one inch here.
00:06:40.160 --> 00:06:43.759
I mean, we have them in flange commercial products up to 14 inch.
00:06:43.759 --> 00:06:44.319
Yeah.
00:06:44.319 --> 00:06:44.879
Yeah.
00:06:44.879 --> 00:06:46.959
I mean, we we make some pretty big stuff.
00:06:46.959 --> 00:06:50.160
I I think I might have a picture of you riding one with a cowboy here.
00:06:50.160 --> 00:06:50.560
Yeah.
00:06:50.560 --> 00:06:52.800
I know you don't have a picture of that.
00:06:52.800 --> 00:06:56.639
That's a fixture I know doesn't exist.
00:06:56.639 --> 00:06:58.160
Oh, it might.
00:06:58.399 --> 00:07:12.319
Uh and one question that we do get um quite a bit is on the sticker or on the instruction sheet, it it shows, you know, supply flowing from right to left, return from left to right, or vice versa.
00:07:12.319 --> 00:07:15.279
Um, people will be like, is that necessary?
00:07:15.279 --> 00:07:18.959
No, it can go either, you can you know, flow in either direction.
00:07:18.959 --> 00:07:23.199
One thing that is important though is that the supply is on the top, return is on the bottom.
00:07:23.199 --> 00:07:28.639
That's gonna be the best, most efficient dirt and air separation um within within that.
00:07:29.360 --> 00:07:30.000
Yeah, yeah.
00:07:30.000 --> 00:07:36.480
That and then your your primary is one side, secondary is the other side, or boiler or building, however you want to classify that.
00:07:36.480 --> 00:07:40.800
Yo stays consistent on on the same side of the of the separator.
00:07:40.800 --> 00:07:41.199
Sure.
00:07:41.360 --> 00:07:46.079
And the other question we would get an awful lot too is after the fact, of course.
00:07:46.079 --> 00:07:50.720
Um, hey, I pipe the supply in the bottom and the return in the top.
00:07:50.720 --> 00:07:51.759
Will it still work?
00:07:51.759 --> 00:07:53.600
It will still decouple the pumps.
00:07:53.600 --> 00:08:00.319
Yes, it will do that part of it, but you will have some stratification and mixing going on in that barrel regardless.
00:08:00.319 --> 00:08:08.160
So all your warmer, hot or hot water going in through the bottom will then rise up, mix in, and and it'll mess up your return temp.
00:08:08.160 --> 00:08:13.839
It'll boost your return temp into your boiler, which will then in turn affect its efficiencies.
00:08:13.839 --> 00:08:15.920
It won't work as efficiently as it should.
00:08:16.240 --> 00:08:20.160
Well, plus, I mean, the air separation, obviously, that that works by us at the highest temperature.
00:08:20.160 --> 00:08:20.480
Right.
00:08:20.480 --> 00:08:27.279
So if you've got the highest temperature coming in through the bottom and those bubbles are separating out, rising up, now they're getting shot back out.
00:08:27.279 --> 00:08:30.079
And back to the system before they get vented out.
00:08:30.319 --> 00:08:30.639
Yep.
00:08:30.639 --> 00:08:31.519
Exactly.
00:08:31.519 --> 00:08:39.279
So if you ever have questions, you get one of these as your first one, we'll we'll always be happy to answer those questions if you call in.
00:08:39.279 --> 00:08:43.279
Um be curious and ask us questions if you don't know.
00:08:43.279 --> 00:08:43.919
Yeah.
00:08:43.919 --> 00:08:45.440
Yeah, that's what we're here for.
00:08:45.440 --> 00:08:46.080
Yes.
00:08:46.080 --> 00:08:52.639
So from that, we're gonna talk about uh air separators, right?
00:08:52.639 --> 00:09:01.440
We kind of talked about it with a with an air scoop, but I mean this is a better alternative to an air scoop is an air separator, like this 551 we got here.
00:09:01.440 --> 00:09:11.120
Uh coalescing mesh in it, and uh super serviceable air vent, and you know, one inch all the way up to 12 inch, 14 inch.
00:09:11.120 --> 00:09:12.559
It's uh 14 inch, yeah.
00:09:12.559 --> 00:09:13.519
Yep.
00:09:13.519 --> 00:09:17.039
For for our Canadian viewers, uh only 12 inch.
00:09:17.039 --> 00:09:24.960
But uh for uh for the rest of us, uh we we have the ability to make a 14-inch uh air separator.
00:09:24.960 --> 00:09:30.720
So I think just the feather in our cap with this stuff is serviceability.
00:09:30.720 --> 00:09:33.519
Uh you'll always hear me tout serviceability.
00:09:33.519 --> 00:09:34.639
All of us do.
00:09:34.639 --> 00:09:41.600
We can take the air vent apart, we can clean it if it starts to leak, because air vents shouldn't leak water, they should only let air out, right?
00:09:41.600 --> 00:09:41.919
Right.
00:09:41.919 --> 00:09:45.279
But it's easy enough to pull it apart and clean that needle valve assembly out.
00:09:45.279 --> 00:09:49.200
And if you can't get it cleaned out, more than likely the seal might be dried out.
00:09:49.200 --> 00:09:52.559
You know, if you're running a glycol system, glycol's hard on stuff.
00:09:52.559 --> 00:09:53.919
Very hard, very hard.
00:09:54.080 --> 00:09:55.759
It's hard to get air out of glycol.
00:09:55.919 --> 00:09:59.200
Yeah, it's hard to get air out of glycol because it's so thick, you know.
00:09:59.200 --> 00:10:03.759
Um, and two, it just it's hard on rubber parts.
00:10:03.759 --> 00:10:08.080
It is, and it finds its way out of everything, finds its way to escape.
00:10:08.080 --> 00:10:08.720
Yeah.
00:10:08.720 --> 00:10:11.279
So slippery, it's a slippery little devil.
00:10:12.159 --> 00:10:21.039
Um really nice that they've got the a half-inch female connection to on the bottom for a fill valve, expansion tank, yep, all that stuff.
00:10:21.279 --> 00:10:25.519
And also a pinned float um in the air vent, the discharge assembly.
00:10:25.519 --> 00:10:29.279
There's a a pin in the center of that float that keeps that float moving up and down.
00:10:29.279 --> 00:10:36.879
You know, if you happen to get it installed a little out of a plum, uh that float won't ride against the side of the body and get hung up.
00:10:37.200 --> 00:10:39.600
Yeah, it doesn't mean we should you should forget your level.
00:10:39.600 --> 00:10:46.000
But if you happen to, um if you get it pretty close, it'll still somewhat work.
00:10:46.000 --> 00:10:54.080
Um yeah, it's nice that it is pinned and it doesn't allow it to float or stick to one side or the other of the body.
00:10:54.080 --> 00:10:59.360
You'll always have that float-centered and arrow be able to get around it pretty well.
00:10:59.360 --> 00:11:03.279
We sell the rebuild parts for it.
00:11:03.279 --> 00:11:08.799
So the top, the entire top or coalescing mesh, it's all o-ring sealed together.
00:11:08.799 --> 00:11:13.519
You don't have to worry about gaskets when you do pull them apart to service them or replace parts.
00:11:13.519 --> 00:11:16.240
They always have captured rubber o-rings in them.
00:11:16.399 --> 00:11:22.159
I think that stays on track with you, most of the Clefy products is that again, it's serviceable.
00:11:22.159 --> 00:11:26.080
We we have the the service and maintenance parts and replacement parts.
00:11:26.080 --> 00:11:29.840
Uh like all of our products, we focus on being served on serviceability.
00:11:30.080 --> 00:11:30.480
Yep.
00:11:30.480 --> 00:11:38.399
And you called it out earlier with the SEP4, but where is the ideal location for a an air separator?
00:11:38.960 --> 00:11:42.080
The hottest point and the lowest pressure point in the system.
00:11:42.080 --> 00:11:47.919
So ideally, this would be on the supply upstream of a circulator.
00:11:48.159 --> 00:11:48.879
Yep, yep.
00:11:48.879 --> 00:12:10.720
You can go downstream of it too, but if you what you run into in some cases, if your your circ is oversized, which happens a lot, and it's really close to the inlet side of that circuit, you can create a problem with that circu actually pulling a negative, a pretty hard negative enough to actually pull that float down, and it'll suck air in.
00:12:10.720 --> 00:12:14.559
So we do make a uh a check valve cap for it.
00:12:14.559 -->
00:12:19.840
So an anti-suction cap, which is really nice, but that's kind of a boo-boo fix.
00:12:19.840 --> 00:12:25.919
And the better the the better fix for the boo-boo would be to cut the boo-boo out and start all over.
00:12:25.919 --> 00:12:32.320
But you know, time is money, so sometimes you have to do that.
00:12:32.320 --> 00:12:35.679
Um, but yeah, that's that's the uh the air separator.
00:12:35.679 --> 00:12:38.639
Now we have the dirt separator right there.
00:12:38.639 --> 00:12:41.840
You got that nifty uh clear version there.
00:12:42.000 --> 00:12:44.240
Um yeah, this is a you can take a look inside.
00:12:44.240 --> 00:12:46.080
This is our our dirt make pro.
00:12:46.080 --> 00:13:01.360
Um these have two magnets, so you've actually got one magnet right in the flow path that will hold all kinds of any any ferrous material until you you know shut it down, pull that pin, everything obviously falls down to the bottom.
00:13:01.360 --> 00:13:12.639
We've also got another magnet that any ferris material that runs into this mesh and doesn't get stuck to that magnet will be held in place here until you pull that when it's time to purge it down, clean it out.
00:13:13.200 --> 00:13:17.200
Yeah, that's the safety belt and suspenders approach to removing ferris material.
00:13:17.200 --> 00:13:23.039
But what people don't realize, I mean, everybody there was a big push to put magnets in systems, right?
00:13:23.039 --> 00:13:28.399
And reason being pumps, variable speed pumps, variable speed circulators.
00:13:28.399 --> 00:13:30.159
Those are a wet rotor magnet.
00:13:30.159 --> 00:13:35.039
So if you don't have a magnetic dirt separator, you actually do if you have a variable speed pump.
00:13:35.039 --> 00:13:37.360
It's a really expensive one, very expensive, right?
00:13:37.360 --> 00:13:52.720
I always tell the story that like one of the one of my easiest service calls on a hydronic system is we did we did a a job for a guy that uh he had an addition, he added some in floor, and it was an existing system.
00:13:52.720 --> 00:14:00.320
I don't think anybody really looked or paid no mind to it, and this is before we were installing magnets and anything.
00:14:00.320 --> 00:14:00.799
Right.
00:14:00.799 --> 00:14:06.639
Um put a variable speed, was a nice uh Grunfuss alpha pump, I think it was an alpha two or whatever.
00:14:06.639 --> 00:14:10.320
Put it in there, and um, I get a phone call on a Saturday.
00:14:10.320 --> 00:14:14.240
Yeah, you guys did this work in April, it's October, it doesn't work.
00:14:14.240 --> 00:14:16.480
Long story short, go over there.
00:14:16.480 --> 00:14:18.559
I don't have that pump on the truck.
00:14:18.559 --> 00:14:22.879
I take the four bolts loose, I pull the cartridge, and it's covered in that red stuff.
00:14:22.879 --> 00:14:24.799
It's just not not ideal.
00:14:24.799 --> 00:14:29.039
And of course the homeowner's sitting there watching me on the bucket or on the chair.
00:14:29.039 --> 00:14:29.840
Yeah, on the chair.
00:14:29.840 --> 00:14:32.080
Oh no, he was standing and fuming.
00:14:32.080 --> 00:14:41.919
So um, shop rag to the rescue, wipe all the stuff off of it, uh put it back in, did a little purge, got it going, and it ran perfect.
00:14:41.919 --> 00:14:43.519
Well, why is that in there?
00:14:43.519 --> 00:14:45.679
Why did you guys put red stuff in my system?
00:14:45.679 --> 00:14:46.960
We didn't, it was in there.
00:14:46.960 --> 00:14:48.960
No, no, it was fine.
00:14:48.960 --> 00:14:53.600
Well, it was fine because you had you did not have variable speed pumps until we put this one in.
00:14:53.600 --> 00:14:53.759
Right.
00:14:53.759 --> 00:14:56.879
This one's this one attracted all that debris out of the system.
00:14:57.039 --> 00:15:00.399
So it's amazing how much stuff will get in your hydronic system.
00:15:00.399 --> 00:15:00.639
Yeah.
00:15:00.639 --> 00:15:00.879
Yeah.
00:15:00.879 --> 00:15:04.799
It's well, you have to you have to remember that magnetite is almost like a powder.
00:15:04.799 --> 00:15:09.840
So it's like you call it boiler ink or you know, that black magnetite hematoner.
00:15:09.840 --> 00:15:10.080
Yep.
00:15:10.080 --> 00:15:13.440
Um if you dry that out, it's actually a very fine powder.
00:15:13.440 --> 00:15:14.080
Like soil.
00:15:14.080 --> 00:15:14.799
Core consistency.
00:15:14.799 --> 00:15:15.039
Yeah.
00:15:15.039 --> 00:15:16.000
Yeah.
00:15:16.000 --> 00:15:18.799
So that's where the magnetic separation is important.
00:15:18.799 --> 00:15:21.279
And you're right, variable speed pumps will catch that.
00:15:21.279 --> 00:15:31.679
Uh boiler heat exchangers, you know, radiators, anywhere in the system that you have a velocity drop, um, that magnetite will settle out in.
00:15:31.840 --> 00:15:32.320
Yeah.
00:15:32.320 --> 00:15:40.799
Pastine rads are great little spots for stuff to hide, and you can't put enough pressure through them things with all the ripples that are in that surface.
00:15:40.799 --> 00:15:43.679
The larger passages that bot that velocity drops.
00:15:43.679 --> 00:15:45.039
It does, it drops big time.
00:15:45.519 --> 00:15:45.919
Radiator.
00:15:45.919 --> 00:15:47.759
Yeah, perfect dirt separators.
00:15:47.759 --> 00:15:48.320
Yes, yeah.
00:15:48.320 --> 00:15:48.960
Radiators.
00:15:48.960 --> 00:15:49.840
Yeah, they are.
00:15:49.840 --> 00:15:53.360
Well, we always say if you don't have a dirt separator, your system becomes one.
00:15:53.360 --> 00:15:54.000
Yep, yep.
00:15:54.159 --> 00:15:54.480
Exactly.
00:15:54.480 --> 00:15:56.240
Yep, all the nooks and crannies.
00:15:56.240 --> 00:16:06.480
Well, I I think we covered air separators, dirt separators, hydraulic separators with air and dirt, and now we have the air dirt.
00:16:06.480 --> 00:16:08.799
So where would we put in an air dirt?
00:16:08.799 --> 00:16:13.120
That is number one question that we get about that product.
00:16:13.120 --> 00:16:14.159
Where do we put it?
00:16:14.159 --> 00:16:20.960
I had a supplier in Colorado that I went and visited, and he's like, Oh, yeah, we love Cleffy products.
00:16:20.960 --> 00:16:24.799
Okay, you don't sell a lot of them, but that's cool that you love them.
00:16:24.799 --> 00:16:27.519
Um what one do you sell the most of?
00:16:27.519 --> 00:16:28.480
I'm just curious.
00:16:28.480 --> 00:16:30.000
Oh, the 546.
00:16:30.000 --> 00:16:31.919
Well, why do you sell the 546?
00:16:31.919 --> 00:16:35.919
Well, because it's an air and a dirt, and our plumbers just want one thing and it's simple.
00:16:35.919 --> 00:16:39.919
Okay, where are your plumbers installing these on boiler systems?
00:16:39.919 --> 00:16:41.279
Well, I don't know.
00:16:41.279 --> 00:16:42.559
They just install them.
00:16:42.559 --> 00:16:46.240
Well, uh let me let me ask this question.
00:16:46.240 --> 00:16:50.240
Where does dirt where where do you what do you want to protect?
00:16:50.240 --> 00:16:52.960
Well, we want to protect the whole system.
00:16:52.960 --> 00:16:58.000
Okay, where is where's the best place to remove air from the system?
00:16:58.000 --> 00:17:00.399
And they just kind of looked at me because they're counter guys.
00:17:00.399 --> 00:17:07.519
I said, the best place to remove air from a system, a hydronic system, a heating system, is the hottest water with the lowest velocity.
00:17:07.519 --> 00:17:18.799
Usually in the supply, you know, up here in farm country, we like to put our our cast iron boilers in the basement, and we come up right off of it and we we put that air separator right there.
00:17:18.799 --> 00:17:19.279
Exactly.
00:17:19.279 --> 00:17:23.599
On the supply before it goes out to any baseboards or radiators or whatever.
00:17:23.839 --> 00:17:24.000
Yep.
00:17:24.079 --> 00:17:29.920
Highest temperature water, highest temperature water that's gonna you're essentially boiling, right?
00:17:29.920 --> 00:17:36.160
It may not be the right term, but simple term, boiling and creating bubbles right there.
00:17:36.160 --> 00:17:36.559
Right.
00:17:36.559 --> 00:17:38.880
Okay, that's where you're gonna remove the the air.
00:17:38.880 --> 00:17:42.640
So now I see, you know, the squirrel's turning the wheel a little bit.
00:17:42.640 --> 00:17:49.200
I said, but you want to protect your boiler, right, from any dirt and debris coming back.
00:17:49.200 --> 00:17:52.319
And you want to protect a variable speed pump if that's what they're using.
00:17:52.319 --> 00:17:54.480
And they just kind of got quiet.
00:17:54.720 --> 00:17:58.160
Well, and it's gonna do that, but it's gonna do it from the supply side.
00:17:58.160 --> 00:18:01.759
It will, but but it's too late because it's already caught in the boiler.
00:18:01.759 --> 00:18:02.240
I agree.
00:18:02.240 --> 00:18:16.160
You know, yeah, I look at a system that has an air separator on the high side where the water's the warmest and you're gonna get the most efficient air separation, uh, and then a dirt mag on the return side before the boiler and the pump to protect the pump.
00:18:16.160 --> 00:18:22.559
I mean, you're gonna get both out of that, but it's hard to get it in that ideal spot for either one.
00:18:22.880 --> 00:18:23.359
Right.
00:18:23.359 --> 00:18:32.960
So I said you should be selling them, you know, you should be talking to these guys about putting an air separator on one on the supply and a dirt separator on the other.
00:18:32.960 --> 00:18:36.240
That device there works as like a band-aid.
00:18:36.240 --> 00:18:36.720
Right.
00:18:36.720 --> 00:18:43.279
You know, say they got an air separator in, but they figure, well, we're gonna do double duty, we're gonna do some more air removal.
00:18:43.279 --> 00:18:45.440
I would still put that on the return anyway.
00:18:45.440 --> 00:18:45.680
Yeah.
00:18:45.680 --> 00:18:46.799
On your boiler system.
00:18:47.279 --> 00:18:50.079
Those are fantastic for chiller systems, though.
00:18:50.079 --> 00:18:50.640
Exactly.
00:18:50.640 --> 00:19:02.400
That's the perfect application because on the chiller system, you know, the return side before the equipment and the pump is where you're gonna want to do your dirt removal, but that's also where your water temperature is the warmest and you get your best air separation.
00:19:02.400 --> 00:19:03.839
Yep, that's the warm side.
00:19:03.839 --> 00:19:04.559
Yep.
00:19:04.559 --> 00:19:09.039
So that's really the best application for an air dirt, is in a chiller.
00:19:09.200 --> 00:19:09.359
Yeah.
00:19:09.359 --> 00:19:12.160
That's where you can get that in the ideal spot for bolt.
00:19:12.319 --> 00:19:12.559
Right.
00:19:14.000 --> 00:19:21.359
Well, and I think that's I mean, that's the best option to get rid of any materials, not just ferrous materials, too.
00:19:21.359 --> 00:19:24.000
I'm like, we look at this has got coalescing mesh in it.
00:19:24.000 --> 00:19:31.839
Yeah, it's gonna help you remove that ferrous material, but let's be honest, not all jobs are neat and tidy, right?
00:19:31.839 --> 00:19:42.960
You get you get an apprentice, you get an apprentice that you know likes to put they're under the mindset a little is good, more is better with flux and solder or thread tape.
00:19:42.960 --> 00:19:46.480
I mean, how many of these have we probably blown off and gotten thread tape out of?
00:19:46.480 --> 00:19:47.119
Yeah, you know.
00:19:47.359 --> 00:19:51.359
Well, that coalescing mesh is gonna take care of the more of the non-ferrous material.
00:19:51.359 --> 00:19:51.839
Exactly.
00:19:51.839 --> 00:19:53.519
The magnets there for the ferrous.
00:19:53.680 --> 00:19:54.000
Yep.
00:19:54.000 --> 00:19:54.319
Yep.
00:19:54.319 --> 00:19:58.640
So you kill two birds with one stone then you have all that in there.
00:19:58.640 --> 00:20:06.640
Um keeping systems clean from you know the solids, that's what these devices are for.
00:20:06.640 --> 00:20:11.039
We get other questions about hey, what about water
quality?
00:20:11.039 --> 00:20:12.799
Totally different animal.
00:20:12.799 --> 00:20:15.599
I mean, that's another approach that has to be taken.
00:20:15.599 --> 00:20:28.480
That is treatment of the fluid, that is putting in good fluid, like the mineralized water, but then you still got to add inhibitors to it because nice, clean, good water looks to rebalance itself.
00:20:28.480 --> 00:20:31.839
When we're talking, you know, RO is the most aggressive, right?
00:20:31.839 --> 00:20:34.720
Like you would never put RO in a system because it'll eat it alive.
00:20:34.720 --> 00:20:38.319
There's a reason it's piped in plastic and nothing, nothing else, right?
00:20:38.319 --> 00:20:39.039
Right.
00:20:39.039 --> 00:20:56.400
Um, but demineralized is less aggressive, but still aggressive enough where it's going to try and leach minerals out of any components that are in their cast iron volutes, um, iron-bodied separators, you know, brass, brass will give up some, some grades of stainless will give up some.
00:20:56.400 --> 00:20:58.960
So it'll always work to rebalance.
00:20:58.960 --> 00:21:00.480
Yep, it always works to rebalance.
00:21:00.480 --> 00:21:07.519
Doesn't mean it's bad water, it just turns from nice clear liquid to kind of a rusty tea color.
00:21:07.519 --> 00:21:09.039
So keep that in mind.
00:21:09.039 --> 00:21:13.599
If you got hard water and you're putting it in there, you get all the solids out, great.
00:21:13.599 --> 00:21:27.200
But if you have a boiler that over time all of a sudden has a lot of kettling going on and heat transfer is not good, that's usually that usually means that there's not so good of water quality in there.
00:21:27.440 --> 00:21:31.200
Yeah, I mean, water quality is your number one first starting point.
00:21:31.200 --> 00:21:40.720
If you start with a clean system and you put in water with you know very high quality water, these devices are there to protect and maintain the system from there.
00:21:40.720 --> 00:21:43.119
But let's let's start fresh and start clean.
00:21:43.119 --> 00:21:48.880
You know, if you are in an old system, um retrofitting an old system, these will be there to help clean that up.
00:21:48.880 --> 00:21:49.359
Right.
00:21:49.359 --> 00:21:52.400
And water quality will keep all your components running good.
00:21:52.400 --> 00:21:54.799
Yeah.
00:21:54.799 --> 00:21:57.200
It's a big uh it's a big thing.
00:21:57.200 --> 00:21:58.160
It is a big thing.
00:21:58.160 --> 00:21:58.559
It is.
00:21:58.559 --> 00:21:59.200
Little did we know.
00:21:59.200 --> 00:21:59.680
Yeah.
00:21:59.680 --> 00:22:00.480
Exactly.
00:22:00.480 --> 00:22:07.759
Whether it's a small residential project or you know large commercial, I mean Caleffi has you protect it.
00:22:07.759 --> 00:22:08.160
Right.
00:22:08.160 --> 00:22:10.640
Got a product to to fit your application.
00:22:10.880 --> 00:22:11.599
Absolutely.
00:22:11.599 --> 00:22:14.160
And uh if you need help, give us a call.
00:22:14.160 --> 00:22:14.799
Yeah.
00:22:15.039 --> 00:22:15.599
We're here.
00:22:15.839 --> 00:22:16.480
We are.
00:22:16.480 --> 00:22:18.319
Thanks everybody.
00:22:18.480 --> 00:22:18.720
Thank you.
00:22:18.720 --> 00:22:19.359
Yeah, everybody.
00:22:19.359 --> 00:22:20.720
Talk to you later.
00:22:22.799 --> 00:22:24.400
Well, that's a wrap for this episode.
00:22:24.400 --> 00:22:26.160
Got questions or stories to share?
00:22:26.160 --> 00:22:27.440
We'd love to hear from you.
00:22:27.440 --> 00:22:29.839
Reach out and let's keep this conversation going.
00:22:29.839 --> 00:22:32.799
Don't forget to subscribe and leave a review wherever you listen.
00:22:32.799 --> 00:22:37.119
Until next time, stay curious and keep your systems running smoothly.