00:00:01.679 --> 00:00:05.919
Welcome to the Ask Coleffi podcast coming at you live from the land.
00:00:06.320 --> 00:00:07.919
Guys, what do we got going on?
00:00:08.160 --> 00:00:13.199
Plumbing, hydronics, expert insights, and a few stories from the trenches.
00:00:13.519 --> 00:00:18.399
Whether you're on the job or just along for the ride, we've got you covered.
00:00:20.719 --> 00:00:27.519
Hey, welcome back to another episode of the Ask Calefi podcast with Larry Mo Curly and Champ.
00:00:29.679 --> 00:00:30.480
You like that?
00:00:30.640 --> 00:00:30.879
Yeah.
00:00:31.039 --> 00:00:31.280
Yeah.
00:00:31.600 --> 00:00:32.479
It worked out pretty good.
00:00:32.560 --> 00:00:34.880
You knew nothing was coming out of my mouth at all.
00:00:35.439 --> 00:00:35.759
No.
00:00:35.920 --> 00:00:36.960
That's awesome.
00:00:37.280 --> 00:00:39.840
So uh talk a little PRV today.
00:00:40.079 --> 00:00:41.359
Yeah, PRVs.
00:00:41.679 --> 00:00:44.000
We have a few models, don't we?
00:00:44.240 --> 00:00:44.799
Yeah.
00:00:45.359 --> 00:00:46.560
A couple to pick from.
00:00:48.000 --> 00:00:49.200
A couple to pick from.
00:00:50.479 --> 00:00:55.759
Our uh 535, our 536, and our 533.
00:00:56.240 --> 00:00:58.240
And well, that would be your domestic.
00:00:58.320 --> 00:01:02.880
And then we got our combo fill line right there.
00:01:03.119 --> 00:01:03.359
Yep.
00:01:03.600 --> 00:01:05.439
573 for 573.
00:01:05.840 --> 00:01:06.079
Yep.
00:01:06.159 --> 00:01:10.879
And the 5350, which we don't have in front of us right now, but there's one hanging in the wall over there.
00:01:11.760 --> 00:01:16.000
But yeah, I think uh, you know, we got the 536.
00:01:16.799 --> 00:01:21.680
The big boy, big dog, uh, for handling some uh pretty high pressures.
00:01:22.239 --> 00:01:26.480
And then the rest of these are really for you know a standard application, so to speak.
00:01:26.719 --> 00:01:26.959
Right.
00:01:27.120 --> 00:01:27.359
Right?
00:01:27.920 --> 00:01:33.439
So, but uh the 536 is a pretty pretty meaty product.
00:01:33.840 --> 00:01:34.319
Yeah, it is.
00:01:34.480 --> 00:01:37.680
So it's the piston design versus the diaphragm.
00:01:37.920 --> 00:01:41.200
And that'll take pressures down 150 to 90.
00:01:41.439 --> 00:01:45.120
Yeah, yeah, 90 to 150 adjustable on the high pressure.
00:01:45.200 --> 00:01:45.439
Yep.
00:01:45.519 --> 00:01:52.640
Um, and then we do have a low pressure from 10 to 90 psi with a 10 to 90 psi range.
00:01:52.799 --> 00:01:54.400
Yep, and that's a 535.
00:01:54.560 --> 00:02:06.079
Yeah, so really robust for uh you know any application where you know water quality might be an issue or you know, changing water pressures or surging water pressures, that thing's gonna be really robust.
00:02:06.400 --> 00:02:10.800
And we also offer a kit with them both together, yeah, which is new.
00:02:11.039 --> 00:02:16.000
Yeah, that uh a double reduction kit, we'll call it, right?
00:02:16.159 --> 00:02:21.919
Right, two stage, two stage, two stages of uh of reduction.
00:02:22.240 --> 00:02:27.199
Matt, I'm gonna pick on you because you're just smiling over there, nodding your head, going, Oh, they're covering it pretty good.
00:02:28.240 --> 00:02:28.560
I did.
00:02:28.879 --> 00:02:31.039
We're gonna get through this because I don't have to be involved.
00:02:31.120 --> 00:02:31.520
Uh-huh.
00:02:31.919 --> 00:02:33.280
Not so fast.
00:02:34.080 --> 00:02:37.840
Uh you've probably run across these in the past.
00:02:37.919 --> 00:02:46.319
I mean, we all have talked to people on the phone about them, and I've been out to visit some job sites where they definitely need double reduction because they're blowing up PRVs.
00:02:46.479 --> 00:02:50.960
But kind of take us through why you would want a two-stage reduction.
00:02:51.599 --> 00:02:58.800
So I we really don't recommend um reducing much more than two to one in a single stage.
00:02:58.960 --> 00:03:06.800
So if you've got you know 150 psi coming in, you're reducing it to 70, 75 psi one stage, fine, no problem.
00:03:07.039 --> 00:03:11.840
Uh, but there's areas where you're gonna have you know 200 plus psi coming in.
00:03:12.000 --> 00:03:18.960
Um at that point, you want a piston style, like our 536, to take that, you know, knock it in half.
00:03:19.039 --> 00:03:26.719
Say you've got you know 220 coming in, knock that down to 110 right here, and then you take it the rest of the way down with our 535.
00:03:27.520 --> 00:03:34.000
Yeah, and those are systems you it's usually higher elevation, they're boosting from a lower elevation.
00:03:34.319 --> 00:03:36.639
There's you know, high rises, yeah.
00:03:36.879 --> 00:03:41.599
The Carolinas in particular, like near the smokies, there's a lot of boosted systems.
00:03:41.840 --> 00:03:50.800
So they need 200 psi at the bottom to get it to the top of some of the areas that they're uh they're trying to you know fulfill the the need.
00:03:51.120 --> 00:03:53.680
So that is where you're gonna run into something like that.
00:03:53.840 --> 00:04:04.879
Out west is another place, you know, Wyoming, Idaho, that kind of thing, where in the bottom where all the municipal stuff is, they're gonna boost to get it up the hill.
00:04:05.120 --> 00:04:05.599
Absolutely.
00:04:05.680 --> 00:04:11.680
Well, yeah, same with any basically any store or six, seven, eight-story building plus.
00:04:11.919 --> 00:04:13.680
Yeah, high rises in big cities.
00:04:15.120 --> 00:04:15.680
Yeah.
00:04:15.840 --> 00:04:24.160
Um, I think what's cool about our stuff, and you're never not gonna hear it about from us, is uh the serviceability of all of our stuff, right?
00:04:24.639 --> 00:04:29.439
Uh you know, even the 533 as a very price competitive model.
00:04:30.160 --> 00:04:32.160
Uh you can take that thing apart.
00:04:32.879 --> 00:04:39.040
You are limited with the 533 in you know sizes, your half and three-quarter, that's all you're gonna get.
00:04:39.120 -->
Load full transcript
00:04:39.439
Yep.
00:04:39.600 --> 00:04:43.839
Um, there's talk of a slightly revised version coming out.
00:04:43.920 --> 00:04:46.800
We'll see what that looks like in the future here.
00:04:47.040 --> 00:04:56.800
Uh, but for the most part, we're gonna stick with that same half and three-quarter inch sizes because it's a bargain, really, in comparison to some of the other BRVs out there.
00:04:57.360 --> 00:05:07.120
Um what I really think is cool about our product, aside from that you can tear it apart and service it and clean it or replace parts, is we have the gauge.
00:05:07.439 --> 00:05:07.759
Right.
00:05:08.079 --> 00:05:13.680
You don't see a lot of our competitors out there with pressure gauges, and um, it's a nice feature to have.
00:05:14.000 --> 00:05:15.199
It certainly is.
00:05:15.439 --> 00:05:24.560
Um to be able to walk up to a PRV, install it, and then not have to wander back to the truck or forget your test gauge.
00:05:24.800 --> 00:05:27.839
Test gauge or else on someone else's garden hose bit.
00:05:28.079 --> 00:05:28.879
Yeah, right.
00:05:28.959 --> 00:05:30.160
Yeah, it's kind of nice.
00:05:30.399 --> 00:05:35.120
You'd be able to thread that gauge in there uh and uh and do your setting.
00:05:35.360 --> 00:05:35.759
Right.
00:05:35.920 --> 00:05:36.560
Yeah.
00:05:37.120 --> 00:05:57.680
Now one thing to keep in mind too though, um, with with our kit that we saw, our two-stage kit, um, we do have a little thermal expansion device that comes with it that screws in there because in between those two PRVs, if you think of them almost like like check valves essentially, you will have some thermal expansion when there's no flow going through it.
00:05:57.839 --> 00:06:05.439
Um so there is a device that you've got two ports on the 536, one on one side, one on the other side.
00:06:05.600 --> 00:06:13.519
Whichever one is more advantageous to have your pressure gauge screwed into, put that one there, and you put the uh expansion device on the other side.
00:06:13.759 --> 00:06:16.480
It's usually the one facing you as you walk up to it, right?
00:06:16.720 --> 00:06:17.439
Usually, yeah.
00:06:17.600 --> 00:06:17.920
Yeah.
00:06:18.079 --> 00:06:20.879
And that is uh it's a liquid-filled gauge, which is really nice.
00:06:20.959 --> 00:06:29.680
And when you have high pressure systems, just like you know, our old refrigerant days, yeah, uh liquid-filled gauges don't bounce around a whole lot.
00:06:29.920 --> 00:06:33.759
So uh with higher pressures, it's nice to have a liquid-filled gauge in there.
00:06:34.560 --> 00:06:35.519
Yes, it is.
00:06:36.000 --> 00:06:38.959
What are some of the questions we get?
00:06:39.040 --> 00:06:41.519
And I say this with a smirk on my face.
00:06:42.240 --> 00:06:52.480
But when we get one installed out there, whether it's new or it's been installed for a month, I mean, let's let's talk about some of those calls that we get about these.
00:06:52.560 --> 00:07:04.319
I mean, my favorite is is it is uh it's creeping up overnight, yeah, or it's creeping up after 20 minutes and it's just so happens to be 90 degrees outside.
00:07:04.639 --> 00:07:06.319
What is going on there?
00:07:07.839 --> 00:07:14.160
Well, any one of them don't don't answer all at once.
00:07:14.800 --> 00:07:24.079
Um well uh pressure creep, uh a lot of times I'll I'll well most of the time I'll tell everybody is take that thing apart and check for dirt and debris in there.
00:07:24.319 --> 00:07:29.680
Um that valve won't seat all the way when there's dirt, debris, crud in there.
00:07:29.759 --> 00:07:36.959
And yeah, sometimes you gotta take that cartridge out, take a small little toothbrush, brush around in there, get everything out.
00:07:37.199 --> 00:07:48.000
Um it's it's funny the last month I would say, maybe a little more, been getting a bunch of calls just because of municipalities flushing out fire hydrants.
00:07:48.079 --> 00:07:48.160
Right.
00:07:48.319 --> 00:07:48.560
Yep.
00:07:48.720 --> 00:07:54.720
Um, I had one guy actually last week call and he just didn't have good flow going through.
00:07:54.800 --> 00:08:02.720
And he noticed that he turned on his faucet, and here he had just dark colored water coming out for just a split second.
00:08:02.959 --> 00:08:05.519
And he went down there, he actually called me back.
00:08:05.759 --> 00:08:09.279
He said that screen was completely plugged.
00:08:10.160 --> 00:08:10.959
So took it out.
00:08:11.040 --> 00:08:13.040
I mean, home don't homeowner did it himself.
00:08:13.120 --> 00:08:16.079
He valved it off, had valves on both sides, which was awesome.
00:08:16.319 --> 00:08:21.920
Praised the plumber for that, and serviced it and put it back in, up and running, and away you went.
00:08:22.000 --> 00:08:24.720
So nice, nice, yeah, yeah.
00:08:25.279 --> 00:08:34.639
Yeah, I yeah, I mean you're right though, flushing hydrants will stir up a lot of debris in that system, and that debris pre pressure-reducing valves don't do not like debris.
00:08:34.879 --> 00:09:02.799
No, well, and what causes it is you have a system that's constant under pretty pretty much a steady pressure, and then you take it down, and then everything kind of has the chance to settle out, and then you you increase that pressure, which increases velocity, and it rattles everything loose off the pipes that have been grown, all the biologics, all the rust and stuff that's stuck to the side of the pipe has now been knocked loose and it goes goes downstream.
00:09:03.200 --> 00:09:08.480
Just kind of scours the sides of the walls of that pipe and and deposits it anywhere it can, really.
00:09:08.639 --> 00:09:11.919
Um, which I mean, that's again with how serviceable these are.
00:09:12.080 --> 00:09:14.799
It's got that stainless steel screen inside of there.
00:09:14.960 --> 00:09:16.320
That's gonna catch most of it.
00:09:16.480 --> 00:09:21.200
You just pop that cartridge out, clean that screen off, put it
back in, and you're back in business.
00:09:21.519 --> 00:09:23.600
Yeah, that works out very well.
00:09:23.759 --> 00:09:26.320
Um to be able to pull it apart.
00:09:26.399 --> 00:09:31.360
I mean, even more advantageous might be to install a Y strainer if that's a continuous problem, right?
00:09:31.759 --> 00:09:32.080
Right.
00:09:32.240 --> 00:09:46.960
Um we know people offer these kitted out with Y strainers, and that's a possibility in the near future here, too, is to be able to we have Y strainers in the catalog, you could easily pick up a Y strainer and put it right in front of it if you have room in the piping, right?
00:09:47.200 --> 00:09:48.240
Yeah, that's always the case.
00:09:48.480 --> 00:09:55.840
Yeah, so debris in the cartridge could show you know a slow pressure creep or it could show a quick pressure creep.
00:09:56.000 --> 00:09:56.320
Correct.
00:09:57.279 --> 00:10:01.039
So I mean the debris, you know, could be an indicator of that.
00:10:01.120 --> 00:10:09.600
I mean, if you do have a slow pressure creep over overnight with no use, um that could be thermal expansion in your system as well.
00:10:09.840 --> 00:10:10.799
I was just gonna ask.
00:10:10.879 --> 00:10:11.919
So what else could it be?
00:10:12.399 --> 00:10:14.960
You covered it beautifully, you walked right into that trap.
00:10:15.120 --> 00:10:15.519
Nice.
00:10:15.919 --> 00:10:20.000
To uh so go ahead and and care to explain that phenomenon.
00:10:20.320 --> 00:10:29.840
I mean, anytime you add a PRV to a home or have a PRV in a home, you should have an expansion tank, and those are usually installed at the cold side of the hot water heater of your water heater.
00:10:30.399 --> 00:10:39.279
Um, and what's nice about that is you know, as that heat water heater heats the water, you know, that water expands, which means pressure is gonna increase.
00:10:39.360 --> 00:10:41.600
So that's what that thermal expansion tank is gonna do.
00:10:41.679 --> 00:10:43.120
It's gonna absorb that pressure.
00:10:43.360 --> 00:10:44.000
Right.
00:10:44.320 --> 00:10:46.720
That is always another question I ask too.
00:10:46.879 --> 00:10:48.799
Yeah, thermal expansion tank on.
00:10:48.879 --> 00:10:49.519
Oh no.
00:10:49.759 --> 00:10:52.720
Well, that that would be a good thing to do.
00:10:52.879 --> 00:10:54.159
Yeah, must have.
00:10:54.240 --> 00:10:55.440
Yeah, um, absolutely.
00:10:55.679 --> 00:11:11.440
So ours, ours doesn't have the old school feature of that thermal bypass, that little check that is in some of the older models of other brands, where it will allow water pressure to to bleed off back to the inlet side of the valve.
00:11:12.720 --> 00:11:14.480
Municipalities don't want to see that.
00:11:14.720 --> 00:11:25.440
I mean, it's not like it's not like you want to you don't want that kind of thing happening in a worst case scenario where you have some sort of back siphoning.
00:11:26.159 --> 00:11:32.480
There's enough check valves in the system you'd think that wouldn't be a problem, but you better be safe than sorry.
00:11:32.799 --> 00:11:50.159
Well, and I mean another thing is too, if you supposing you've got one that does have that thermal bypass in it, and you don't have an expansion tank downstream, that uh that pressure still has to creep up in your system above the the incoming pressure before that kind of kicks in.
00:11:50.240 --> 00:11:53.440
So you still have real high pressure in your system at that point.
00:11:53.759 --> 00:11:54.639
Valid point.
00:11:54.799 --> 00:11:55.840
Very valid point.
00:11:55.919 --> 00:11:59.120
And that's not prone to failure either, is it at all?
00:11:59.440 --> 00:12:00.960
No, never.
00:12:02.559 --> 00:12:03.519
Uh yeah.
00:12:04.159 --> 00:12:09.440
Uh what about I think we cover auto have autofills a little bit.
00:12:09.519 --> 00:12:14.320
I mean, they they are a PRV when you're talking of boiler system autofill.
00:12:14.639 --> 00:12:22.159
Uh they provide water flow into your hydronic heating system or chilled water application in some cases.
00:12:22.399 --> 00:12:31.840
Uh most of the time they're companioned with a backflow preventer, and it's not uncommon to see a backflow preventer not too far away from a PRV either.
00:12:32.639 --> 00:12:33.600
Yeah, absolutely.
00:12:33.759 --> 00:12:36.240
I mean, it's backflow preventers.
00:12:36.320 --> 00:12:40.879
I mean, RPs in municipal water supply, you know, larger buildings, especially.
00:12:41.039 --> 00:12:44.960
I mean, they're they're pretty much ubiquitous at this point, they're everywhere.
00:12:45.120 --> 00:12:47.600
Um, and it's for safety's sake.
00:12:47.679 --> 00:12:52.240
I mean, there's you never know when you're gonna need it, but you really want to have one.
00:12:52.399 --> 00:12:59.519
You need to absolutely yeah, just attend any Union Hall uh backflow prevention class and you see some pretty cool horror stories, don't you?
00:12:59.759 --> 00:13:00.080
Oh yeah.
00:13:00.639 --> 00:13:02.080
Yeah, it's it's crazy.
00:13:02.240 --> 00:13:05.600
I mean, it saves saves a lot of lives, to be honest with you.
00:13:05.840 --> 00:13:12.399
Um, these in this case for a boiler fill, that is required everywhere at every boiler fill.
00:13:12.559 --> 00:13:20.320
Um, so if you're if you see a boiler fill valve, ours or anybody else's, you should should see a backflow preventer right there, too.
00:13:20.399 --> 00:13:21.519
Yeah, yep.
00:13:22.320 --> 00:13:31.919
Another one that I hear a bunch about uh that I remember taking a lot of calls about, uh trouble wise, is hey, there's a hammer in my system.
00:13:32.080 --> 00:13:41.919
Like when someone flushes a toilet or there's a small demand, or hey, the kids love to play with the uh the faucet and turn it on and like to hear the pipe slam.
00:13:42.240 --> 00:13:44.960
What can what can we rulle darn kids?
00:13:45.200 --> 00:13:48.480
Darn kids what can we do to prevent that hammering?
00:13:48.559 -->
00:13:56.879
Because it seems like once it starts, it's a shockwave that just continues on with water pressure flowing until we shut the water off completely and then turn it back on.
00:13:57.039 --> 00:13:58.720
What is going on with that?
00:13:59.120 --> 00:14:00.799
There's a couple of things that cause that.
00:14:00.960 --> 00:14:04.559
Um, so one could be your screen is plugged up.
00:14:04.720 --> 00:14:13.039
Um if it's a if you've had this you know installed for months, a year, years, and it's a newer issue.
00:14:13.200 --> 00:14:15.360
My guess would be your screen is plugged up.
00:14:15.440 --> 00:14:24.639
If nothing else has changed in your system, anything like that, that would be the first place that I would check because that essentially is saying like this cartridge is kind of starved for water.
00:14:24.960 --> 00:14:35.120
So a little bit will come through on a demand, this will open up, and then it'll slam shut, and that can happen kind of bang, bang, bang, bang, bang.
00:14:35.519 --> 00:14:38.799
Um and you'll hear kind of almost like a machine gun.
00:14:39.120 --> 00:14:42.879
So if you check your screen, that's all good and clean and everything like that.
00:14:43.519 --> 00:14:52.080
Um if it's a new install and it's kind of starting to happen right off the bat, my guess would be it's oversized for that application.
00:14:52.399 --> 00:14:52.799
Right.
00:14:53.279 --> 00:15:07.440
And it's easy to do kind of because you what you when you're picking it out, what you want to pay attention to is the flow rate that you're gonna be experiencing through that rather than the fitting size or the pipe size that you have.
00:15:07.840 --> 00:15:19.039
Um it's not uncommon, it's actually pretty common to have a PRV that is one pipe size below the pipe size that it's serving.
00:15:19.200 --> 00:15:24.720
So if you've got you know a one-inch pipe and you've got a three-quarter PRV in there, that that is very, very common.
00:15:25.519 --> 00:15:31.039
But it's all it's also hard to for a lot of plumbers to kind of wrap their head around that, myself included.
00:15:31.440 --> 00:15:35.840
Well, you have to remember the municipality has their standard line size they run into a building.
00:15:35.919 --> 00:15:38.559
They don't know what that building really needs or requires.
00:15:38.720 --> 00:15:46.879
So they might run a one-inch uh supply line into a building that's maybe two bed, one bath, and sure.
00:15:46.960 --> 00:15:53.759
You know, that that home doesn't will never see the the flow requirement that a one-inch supply line could provide.
00:15:54.080 --> 00:16:04.559
Yeah, that happens happens often, and it's no different with any other product that we sell just because it's line size doesn't mean you necessarily need what that can carry.
00:16:04.799 --> 00:16:07.120
Right every application's different.
00:16:07.360 --> 00:16:12.639
So if you run into something, I think it's smart to call call our tech support.
00:16:12.720 --> 00:16:14.080
We walk you through as much as we can.
00:16:14.240 --> 00:16:19.360
Yeah, let us know the flow rate, let us know the situation, you know what the building needs.
00:16:19.600 --> 00:16:20.240
Yeah.
00:16:20.879 --> 00:16:21.519
Great.
00:16:21.840 --> 00:16:26.159
Well, I think that covers the episode here on PRVs.
00:16:26.320 --> 00:16:28.159
Uh say it one more time.
00:16:28.320 --> 00:16:30.080
If you have any questions, give us a call.
00:16:30.320 --> 00:16:30.960
Give us a call.
00:16:31.039 --> 00:16:32.480
We love to talk.
00:16:33.279 --> 00:16:34.799
Well, that's a wrap for this episode.
00:16:35.039 --> 00:16:36.639
Got questions or stories to share?
00:16:36.799 --> 00:16:37.840
We'd love to hear from you.
00:16:38.000 --> 00:16:40.320
Reach out and let's keep this conversation going.
00:16:40.480 --> 00:16:43.039
Don't forget to subscribe and leave a review wherever you live.
00:16:43.440 --> 00:16:47.759
Until next time, stay curious and keep your systems running smoothly.